5-1
5-1 Operation Selection During Option Error
5
Maintenance Operations
5Maintenance Operations
5-1 Operation Selection During Option Error
You can select whether to trip the Inverter or continue operation ignoring an error when the optional
PG Board causes an error.
Note:Even if 01 has been selected in operation selection at option error, the Inverter trips when an
encoder disconnection error (E60, E70) or
3G3AX-PG
connection error (E69, E79) occurs.
Refer to "2-6 Switch Settings"(page 2-8).
Parameter No.
Function name
Data
Default
setting
Changes dur-
ing operation
Unit
P001
Operation selection at option
1 error
00: Trip
01: Continues operation
00
×
−
P002
Operation selection at option
2 error
00: Trip
01: Continues operation
00
×
−