2-6
2-5 Connection Diagram
2
Design
2-5 Connection Diagram
Note 1: For the terminal connection on the Inverter, refer to the Inverter 3G3RX User’s Manual.
Note 2: For the signal line, use a twisted shield wire and apply the shield coating as illustrated be-
low. Keep the length to 20 m or less. If the wiring length should be 20 m or more by neces-
sity, use a VX application control device RCD-E(remote control device), or CVD-E
(insulated type signal converter). For the encoder line, use a twisted shield wire of 0.75 mm
2
or more. Keep the length to 20 m or less. If the wiring length should be 20 m or longer by
necessity, use a relay amplifier that specifies 5 V line driver output.
FS
FV
FC
Inverter control terminal
Available to assign to
multi-function input
terminals 1 to 8
EP5
EG5
EAP
EAN
EBP
EBN
EZP
EZN
M
EC
Motor with
an encoder
SAP
SAN
SBP
SBN
Pulse train
position command
POK
ZS
DSE
Output
terminal
FW
RV
LAC
PCLR
(Position deviation
clear)
ORT
CM1
Input
terminal
AP
AN
BP
BN
Encoder signal output
STAT
Encoder signal
TM1
TM2
(LAD cancel)
(Orientation)
(Pulse train position
command input
permission)
(Position ready)
(0 Hz signal)
(Excessive speed
deviation)
PG Board
Available to assign to
multi-function output
terminals 1 to 5
Perform insulating treatment.
Ground connection is not required.
Connect to each common
terminal on the PG Board.
Summary of Contents for 3G3AX-PG
Page 1: ...Cat No I564 E1 01 USER S MANUAL 3G3AX PG Encorder Feedback Board ...
Page 2: ......
Page 14: ...12 Contents ...
Page 15: ...Chapter 1 Overview 1 1 Overview 1 1 ...
Page 27: ...Chapter 3 Operation 3 1 Related Parameters 3 1 3 2 Precautions for Operation 3 8 ...
Page 65: ...Chapter 6 Specifications 6 1 Product Specifications 6 1 ...
Page 67: ......