2-5
2-4 Wiring
2
Design
Mounting the Ferrite Cores
The ferrite core mounting method is shown below.
Mount the two provided ferrite cores as below when connecting the encoder cable.
Connect the wire to the EG5 terminal of the 3G3AX-PG Board through the ferrite cores for shielding.
If the ferrite cores cover the shield coating, they fail to work effectively, causing the Inverter to mal-
function. Be sure to fix the ferrite cores or take other appropriate measures so that they do not over-
lap the shield coating.
The shield wire connected to the terminal could become disconnected due to the weight of the ferrite
cores. Be sure to fix the ferrite cores or take other appropriate measures so that the shield wire does
not receive the weight of the ferrite cores.
3G3AX-PG
Ferrite cores
Encoder cable (Shield wire)