4-3 Pulse Train Position Control Mode
4
Functions
Example: Synchronous Operation
For the Inverter (master Inverter) on the main motor side, you can select either the speed control or
pulse train position control mode.
For the Inverter (slave Inverter) on the sub motor side, you need to select the pulse train position
control mode.
Configuration Example
• Main motor
: Number of encoder pulses = 1024
• Sub motor
: Number of encoder pulses = 3000
• Main motor rpm : Sub motor rpm = 2:1
For operation under the above conditions, set the following data in the slave Inverter.
Pulse train mode selection (P013)
: 00 (pulse with 90
°
phase difference)
Electronic gear setting position selection (P019)
: 01 (REF)
Electronic gear ratio numerator (P020)
: 3000
Electronic gear ratio denominator (P021)
: 1024
×
2 = 2048
The following shows an example of the ratio of slave rpm to master rpm depending on the P019 to
P021 settings.
(Note that the same number of encoder pulses (1024 pulses) should be set on both Inverters.)
Electronic gear setting
position selection (P019)
REF
(Position com-
mand side)
REF
(Position com-
mand side)
FB
(Position feedback side)
FB
(Position feedback side)
Electronic gear ratio
numerator (P020)
1024
2048
1024
2048
Electronic gear ratio
denominator (P021)
2048
1024
2048
1024
Slave rpm/
Master rpm
1/2
2
2
1/2
Master Inverter
AP, BP
AN, BN
EG5
EAP, EBP
EAN, EBN
SAP, SBP
SAN, SBN
EG5
EAP, EBP
EAN, EBN
Slave Inverter
M
EC
Main
motor
M
EC
Sub
motor
Summary of Contents for 3G3AX-PG
Page 1: ...Cat No I564 E1 01 USER S MANUAL 3G3AX PG Encorder Feedback Board ...
Page 2: ......
Page 14: ...12 Contents ...
Page 15: ...Chapter 1 Overview 1 1 Overview 1 1 ...
Page 27: ...Chapter 3 Operation 3 1 Related Parameters 3 1 3 2 Precautions for Operation 3 8 ...
Page 65: ...Chapter 6 Specifications 6 1 Product Specifications 6 1 ...
Page 67: ......