Summary of Contents for OME-ET-7000 Series

Page 1: ......

Page 2: ......

Page 3: ...ET 7000 Hardware Connections 17 2 4 Installing the MiniOS7 Utility 19 2 5 Using the MiniOS7 Utility to Assign an IP Address 20 2 6 Enabling the Adobe Flash Player in Your Browser 24 2 7 Configuring th...

Page 4: ...1 Read Coils 95 4 5 2 02 0x02 Read Discrete Inputs 96 4 5 3 03 0x03 Read Holding Registers 97 4 5 4 04 0x04 Read Inputs Registers 98 4 5 5 05 0x05 Write Single Coil 99 4 5 6 06 0x06 Write Single Regis...

Page 5: ...126 Appendix A Node Information Area 126 Appendix B Thermocouple 132 Appendix C Application Notes 133 C 1 Dual Watchdog 133 C 2 Power on Value 134 C 3 Safe Value 136 C 4 AI High Low Alarm 138 C 5 AI H...

Page 6: ...ywhere and also supports the Modbus TCP protocol that ensures perfect integration with SCADA software Furthermore the OME PET 7000 features PoE technology meaning that not only is data transmitted thr...

Page 7: ...the data cable This innovation allows greater flexibility in office design higher efficiency in systems design and faster turnaround time in installation and implementation The OME PET 7000 features...

Page 8: ...one is the usual method through wiring from an external power source External power source should range from 12 VDC to 48 VDC The reason that the second method has been retained is because it might st...

Page 9: ...OME PET 7000 module has a built in web server that allows users to easily configure monitor and control the module from a remote location using a standard web browser Web HMI The Web HMI function enab...

Page 10: ...for Plug and Play The RJ 45 Port supports automatic MDI MDI x meaning that it can automatically detect the type of connection to the Ethernet device without requiring dedicated straight or crossover...

Page 11: ...g Temperature 25 75 C Storage Temperature 30 80 C Humidity 10 90 RH non condensing I O Pair Connection The I O Pair Connection function is used to create a DI to DO AI to AO pair via the Ethernet Once...

Page 12: ...Mbps L2 LED Indicator LED Status Function On Ethernet link detected Off No Ethernet link detected Flashing Ethernet packet received L1 LED Indicator LED Status Function Flashing The OME ET 7000 OME PE...

Page 13: ...Mode This mode is used to execute and run firmware On the OME ET 7000 OME PET 7000 module the operating mode selector switch should usually be in the Normal position The switch should only be moved fr...

Page 14: ...ESD protection capabilities and ensuring that the module is more reliable Choosing either of the following options will provide a better level of protection for the module The OME ET 7000 OME PET 700...

Page 15: ...ET 7000 OME PET 7000 module and can be used as a reference when defining the specifications for any custom enclosures All dimensions are in millimeters For the OME ET 7000Z OME PET 7000Z 72 x 116 x 3...

Page 16: ...Page 11 For the OME ET 7000 OME PET 7000 72 x 123 x 35 I have a strong mind I can finish anything...

Page 17: ...tility and all of the required documentation etc An outline of the directory structure for the files contained on the CD is shown below CD Application Data_Sheet Quick_start PC_Client Modbus TCP Demo...

Page 18: ...e check the package contents If any of the following items are either missing or damaged contact your dealer or distributor OME ET 7000 OME PET 7000 Software Utility CD Quick Start Guide Before operat...

Page 19: ...the wall or by piggybacking it to another module DIN Rail Mounting The OME ET 7000 OME PET 70 00 module includes simple rail clips that can be used to reliably mount it on a standard 35 mm DIN Rail Mo...

Page 20: ...Page 15 Piggyback Mounting The OME ET 7000 OME PET 7000 module has a hole on either side of the casing that can be used for piggyback mounting...

Page 21: ...way to use MiniOS7 configuration mode Tips Warnings Init mode is a method to use MiniOS7 configuration mode and update the software After the update is completed set the switch to the Normal position...

Page 22: ...description of the configuration for simple applications using the OME ET 7000 OME PET 7000 when implementing both PoE and Non PoE solutions Non PoE i Connect the PC to the Ethernet Port via the Hub...

Page 23: ...Page 18 PoE i Connect the PC to the Ethernet Port via the PoE Switch ii Connect the power supply to the PoE Switch which in turn supplies power to the OME PET 7000...

Page 24: ...d files to the OME ET 7000 OME PET 7000 from a PC Step 1 Install the MiniOS7 Utility tool The latest version of the MiniOS7 Utility can be obtained from the companion CD CD Software Tools for MiniOS7...

Page 25: ...default IP address meaning that you must first assign a new IP address to the OME ET 7000 OME PET 7000 before operation The factory default IP settings are as follows Item Default IP Address 192 168 2...

Page 26: ...all MiniOS7 modules on your network Step 3 Click the 192 168 255 1 item in the IP Port field list and then click the IP Settings icon in the toolbar After the search has been completed click the defau...

Page 27: ...button In the IP Settings dialog box you can manually assign an IP Address Mark Address Gateway and Alias or you can use the DHCP function to dynamically assign IP addresses Once the appropriate value...

Page 28: ...arch option from the Connection menu to check the IP settings After completing and saving the settings you should reboot the module and then use the MiniOS7 Utility to perform another search for the m...

Page 29: ...Center The Adobe Flash Player Download Center http get adobe com flashplayer The Adobe Flash Player is subject to change without notice refer to http www adobe com support flashplayer downloads html f...

Page 30: ...e switch is set to the Normal position and then reboot the module Step 2 Open a browser Use a standard internet browser to view the OME ET 7000 OME PET 7000 web pages such as Mozilla Firefox or Intern...

Page 31: ...prompting you to enter your user name and password The factory default user name and password are as follows Step 5 Welcome to the OME ET 7000 OME PET 7000 web interface After logging into the OME ET...

Page 32: ...ET 7000 and then click the I O function tabs to configure and browse the I O functions For more detailed information related to the I O specification pin assignment and I O functions etc for each OME...

Page 33: ...the OME ET 7000 OME PET 7000 web pages from any computer that has Internet access Step 1 Open a browser Use a standard internet browser to view the OME ET 7000 OME PET 7000 web pages such as Mozilla...

Page 34: ...ame and Password After entering the IP address the login dialog box will appear prompting you to enter your user name and password The factory default user name and password are as follows Item Defaul...

Page 35: ...PET 7000 web interface After logging into the OME ET 7000 OME PET 7000 web interface the welcome page will be displayed This web interface provides a number of functions which can be easily accessed v...

Page 36: ...ides a brief introduction to and explanation of the web interface The Overview option links to the welcome page and contains two main parts The top section of the page provides some basic information...

Page 37: ...Page 32 The lower section of the page provides a brief introduction to the web interface...

Page 38: ...Settings page which allows you to access the IP settings and check the software version Basic Settings Provides access to the Basic Settings page which allows you to configure the basic information f...

Page 39: ...teway or router is a system that is used to connect a network with one or more other networks A subnet mask The subnet mask indicates which portion of the IP address that is used to identify the local...

Page 40: ...h configuring the network settings Manual Configuration When using manual configuration all network settings need to be assigned manually Each OME ET 7000 OME PET 7000 module should have a unique IP a...

Page 41: ...providing by OMEGA for use with custom applications MiniOS7 Version This item provides defaults of the version number for the MiniOS7 OS image which is an embedded operating system specifically design...

Page 42: ...Basic Settings The Basic Settings page allows you to perform the following functions A Configure the module information B Configure the web interface information C Reset all parameters to the default...

Page 43: ...the model of the module and can not be modified Module Information The module information field indicates the name of the alias that is used to identify the module To configure the module information...

Page 44: ...corner of the interface for example the company name and web address as per the example below More Information URL This item allows you to specify the URL that will be displayed when the More informat...

Page 45: ...bus Server TCP Port By default TCP IP uses Port 502 To configure the web interface information follow procedure below Step 1 Enter the desired information into the respective fields Step 2 Click the S...

Page 46: ...b interface and can be used to restore the individual settings to their factory default state To reset the settings to their factory default follow the procedure below Step 1 Check the relevant check...

Page 47: ...Default Settings IP Address 192 168 255 1 Gateway 192 168 0 1 Subnet Mask 255 255 0 0 DHCP Disabled Basic Settings Basic Settings Item Factory Default Settings Module Name Depends on the name of the...

Page 48: ...tID 1 Digital Output Item Factory Default Settings Power on Value OFF Safe Value OFF Digital Input Item Factory Default Settings DI Latch Status Disabled DI Counter Disabled Analog Output Item Factory...

Page 49: ...arm Mode Momentary Low Alarm Alarm Limit Value This value varies depending on the model of the module Enable OFF Alarm Mode Momentary Sampling Rate Normal mode 16 bits 10 Hz Normal mode Fast mode 12 b...

Page 50: ...e factory default settings for the items listed in the Authentication menu Account Management Factory Default Settings A default user account consists of an account name Admin and a password Admin Acc...

Page 51: ...u Option The tables below outline the factory default settings for the items listed in the Web HMI menu Web HMI Factory Default Settings Depends on the Modbus setting function of the OME ET 7000 OME P...

Page 52: ...e 47 d Factory Default Settings for the I O Pair Connection Menu Option The table below outlines the factory default settings for the Pair Connection option Pair Connection Factory Default Settings Em...

Page 53: ...ings The contents displayed on this page will be depending on the Modbus functions applicable to the specific the OME ET 7000 OME PET 7000 module Please refer to the user manual for each module for de...

Page 54: ...Page 49 A Common Functions The Common Functions area provides options that allow the settings for the Modbus functions to be configured...

Page 55: ...hannel The digital output channel will then generate the start up value output y Safe Value When communication between the Host PC and the OME ET 7000 OME PET 7000 module interrupted is broken the dig...

Page 56: ...s web page y DI Latched When DI Latch function is enabled once the digital input channel detects any change in input status the input status will be latched and will remain in this condition the latch...

Page 57: ...in detail below Tips Warnings Before selecting the output range for each analog output channel make sure that the jumpers are set properly For more detailed technical specifications related to the ju...

Page 58: ...tput voltage current as it changes from one output voltage current to another Select the most appropriate value from the respective drop down menus y Power on Value A power on value can be set for a s...

Page 59: ...etail below Tips Warnings Before selecting the input range for each analog input channel make sure that the jumpers are set properly For more detailed technical specifications related to the jumper se...

Page 60: ...00 OME PET 7000 modules support sample rates in either Normal or Fast mode Fast mode uses 60 Hz with a 12 bit resolution while Normal mode uses 10 Hz with a 16 bit resolution y 50 60Hz Rejection for A...

Page 61: ...to on y Enable Each analog input alarm can be switched to on or off by clicking the appropriate radio button y Mode The OME ET 7000 OME PET 7000 allows the alarm to be selected as either Momentary or...

Page 62: ...e following options Account Management Provides access to the privilege management page which allows you to manage user accounts and their associated privileges Accessible IP Settings Provides access...

Page 63: ...58 3 3 1 Account Management The Account Management page provides functions that allow the following tasks to be performed A Configuration of user accounts B Restoration of the factory default user acc...

Page 64: ...hich determine the type of operations the user is allowed to perform h Admin This level enables access to all OME ET 7000 OME PET 7000 web site features functions and commands h User This level enable...

Page 65: ...in administrator account named Admin that is created by default The default account cannot be deleted To restore the factory default user accounts perform the followings Step 1 Select the Load Setup D...

Page 66: ...Page 61 3 3 2 Accessible IP Settings The IP Filter Settings page provides functions that allow the following tasks to be performed Configuration of the connection filtering...

Page 67: ...filter can be enabled by selecting the Enable the IP filter table checkbox After this option is selected only requests from the IP addresses included in the list will be allowed access to the module...

Page 68: ...from a single IP address Step 1 Select the Enable the IP filter table checkbox Step 2 Enter the same IP address in both the From IP Address and the To IP Address text boxes The IP address may be the...

Page 69: ...kbox Step 2 Enter the first IP address in the range in the From IP Address and enter the final IP address in the range in the To IP Address text boxes Step 3 Select the Activate the Rule checkbox Step...

Page 70: ...ing options Web HMI Provides access to the I O monitor page which allows you to remotely monitor and control the I O status of the OME ET 7000 OME PET 7000 module Web Edit Provides access to the Web i...

Page 71: ...e that can be used to display real time I O data values and alarms via the LAN or the Internet Real time I O data values and alarms can be monitored at either the local or remote site using any web br...

Page 72: ...ovides functions that enable users to create customized web pages Users can upload specific I O layout diagrams in either bmp jpg or gif format and can define a description for each I O point No HTML...

Page 73: ...default no pages are listed on the initial Web Page Configuration page The OME ET 7000 OME PET 7000 Web Edit function allows the creation of up to 10 user defined web pages A maximum of 10 pages can...

Page 74: ...e a Web page to monitor the I O status of a conveyor system as shown below The I O system contains a sensor that is used to detect the products and a switch that is used to turn the conveyor motor on...

Page 75: ...r bmp format with a maximum file size of 64 kb The recommended resolution for the image to be displayed on the editing Web page is 340 250 pixels After the upload is completed the image information wi...

Page 76: ...g the image it will be displayed in the preview window Step 4 Add the Register Item s that are to be used to read the selected sensor input Click the Edit button from the first row in the Group table...

Page 77: ...s an input use the Modbus Register 0 DI0 and then select Discrete Input as the Register Type and enter the name PHS1 as the Alias as per the figure shown below Step 6 Save the selected sensor settings...

Page 78: ...ster settings the new register item will be displayed in the Group table If you wish to edit the details for an item click the Edit button to access the Edit Group Register page If you wish to delete...

Page 79: ...bus Register 0 DO0 and then select Coil and Write as the Register Type and enter Motor as the Alias as shown in the figure below Step 9 Save the selected sensor settings Click the Save button to compl...

Page 80: ...hand side of the Web Page Configuration window Select the Carriage item and click the Go button to display to the Carriage web page The conveyer image file and the newly created register items will b...

Page 81: ...ion function is a particular feature of the OME ET 7000 OME PET 7000 module that can be used to enable a pair of DI to DO AI to AO via Modbus TCP With the pair connection function enabled the OME ET 7...

Page 82: ...attempts by the OME ET 7000 OME PET 7000 module to reconnect with the remote input device Remote Net ID The Modbus Net ID of the remote device Scan Time The frequency that the remote input device will...

Page 83: ...are Connections Software Configuration The following provides step by step instructions for how to configure the OME ET 7000 OME PET 7000 via the built in web interface In this example the AO0 AO1 of...

Page 84: ...re the AO type for the OME PET 7026 Click the Module I O Settings option in the configuration section of the Main Menu to open the analog Output Settings page and set the voltage current range to 5 V...

Page 85: ...e g 192 168 1 204 Remote TCP Port 502 Connection Timeout 3000 ms Reconnect Interval 5000 ms Remote Net ID 1 Default 1 the Net ID for the OME ET 7017 To determine the Net ID check the Modbus Definitio...

Page 86: ...Page 81 After completing the configuration click the Submit button to save the settings 1 2...

Page 87: ...odule I O Settings option in the Configuration section of the main menu and check the Basic Settings section on the Analog Input page Supply 5 V to AI0 on the OME ET 7017 and then click the Web HMI op...

Page 88: ...Hardware Connections Software Configuration The following provides step by step instructions for how to configure the OME ET 7000 OME PET 7000 via the built in web interface In this example the DO0 D...

Page 89: ...ion to enable the I O pair connection functions Remote IP Address This is the IP address of the OME PET 7044 e g 192 168 1 99 Remote TCP Port 502 Connection Timeout 3000 ms Reconnect Interval 5000 ms...

Page 90: ...utton to save the settings Testing First set the DI0 status on the OME PET 7044 to ON and then click the Web HMI option in the Web HMI section of the Main Menu for the OME PET 7026 and click the DO ta...

Page 91: ...browser and display the main introduction page for the OME ET 7000 OME PET 7000 series of modules which provides more detailed information related to the modules The URL for this link can be changed...

Page 92: ...Page 87 The default URL that the More Information item will link to http www omega com...

Page 93: ...n Ethernet interface The Modbus TCP messaging service provides a Client Server communication between devices connected on a TCP IP network The OME ET 7000 OME PET 7000 module is a Modbus Server meanin...

Page 94: ...PET 7000 module and will listen to all communications that come in on Modbus TCP registered Port 502 The Modbus TCP client uses the standard TCP method for communicating with the OME ET 7000 OME PET...

Page 95: ...es to the original Modbus protocol which allows for transport over the TCP IP layers A dedicated header is used on TCP IP to identify the Modbus Application Data Unit It is called the MBAP Header MODB...

Page 96: ...0x05 Force Single Coil 06 0x06 Preset Single Register 15 0x0F Force Multiple Coils 16 0x10 Preset Multiple Registers Any other function code request will be returned with an error response indicating...

Page 97: ...e taken For example a client can read the ON OFF states of a group of digital input or output or it can read write the data contents of a group of registers When the server responds to the client it u...

Page 98: ...et 4 3 1 Binary A binary item is represented as a single bit within a data word All binary is packed into 16 bits data words which are accessed using function code 01 and 02 Therefore a single registe...

Page 99: ...first entry in the table is required as well as the number of registers that are requested For each of the primary tables the protocol allows individual selection of 65535 data items and the operatio...

Page 100: ...eturned output quantity is not a multiple of eight the remaining bits in the final data byte will be padded with zeros toward the high order end of the byte The Byte Count field specifies the quantity...

Page 101: ...returned input quantity is not a multiple of eight the remaining bits in the final data byte will be padded with zeros toward the high order end of the byte The Byte Count field specifies the quantity...

Page 102: ...contains the high order bits and the second contains the low order bits Here is an example of a request to read analog outputs of OME ET 7026 OME PET 7026 module Request Response Field Name Hex Field...

Page 103: ...order bits and the second contains the low order bits Here is an example of a request to read analog inputs of OME ET 7026 OME PET 7026 module Request Response Field Name Hex Field Name Hex MBAP Head...

Page 104: ...illegal and will not affect the output The normal response is an echo of the request returned after the coil state has been written Here is an example of a request to write DO1 of OME ET 7026 OME PET...

Page 105: ...st returned after register contents have been written Here is an example of a request to write AO1 of OME ET 7026 OME PET 7026 to 55 FF hex Request Response Field Name Hex Field Name Hex MBAP Header 0...

Page 106: ...ction code starting address and quantity of coils forced Here is an example of a request to write a series of 2 digital outputs starting at DO0 The request data content is one byte 02 hex 0000 0010 bi...

Page 107: ...written Here is an example of a request to write two AO registers starting at AO0 Request Response Field Name Hex Field Name Hex MBAP Header 01 MBAP Header 01 02 02 00 00 00 00 00 00 06 06 Unit Identi...

Page 108: ...ividual Modbus requests to a Modbus slave and it can also continually poll send read and write requests to the slave Subsequently you can re run the sequence of commands For each individual Modubs req...

Page 109: ...uery to the OME ET 7026 by clicking the Send button An example of a query to read digital inputs 0 to 1 from the OME ET 7026 at Modbus ID 1 is given below Step 4 If no error occurs a data field of a r...

Page 110: ...nt to test the Modbus connection The complete version of the Modbus Master Tool can be obtained from the companion CD CD Software Modbus_Master_Tool The following are the step by step instruction on h...

Page 111: ...enu when you read write the AO AI Step 3 Click the Connection Connect to set TCP Connection 1 2 3 4 Request Field Name Hex 1 Unit Identifier 01 2 Function Code 01 3 Starting Address Hi 00 Starting Add...

Page 112: ...he Interface field 2 Fill out the OME PET 7026 s IP address in the Remote Server IP 3 You can keep the settings of other fields or change them then click OK Now the DO status of OME PET 7026 will show...

Page 113: ...ee of change The DLL based on the official releases from http nmodbus googlecode com was verified and improved Programmer can use the DLL released to develop a Modbus application for regular Windows b...

Page 114: ...model number of OME ET 7000 OME PET 7000 e g OME ET 7017 can use type 07 1A Type Code 00 01 02 03 04 05 06 07 Zero Input 0 mV 0 mV 0 mV 0 mV 0 V 0 V 0 mA 0mA Span Input 15 mV 50 mV 100 mV 500 mV 1 V 2...

Page 115: ...Modbus Master Tool can be obtained from the companion CD CD Software Modbus_Master_Tool 4 1 Please double click the ModbusMasterToolPC exe to open it and click the Setup Definition in menu bar to setu...

Page 116: ...command of ch0 1 run W Pulse Note When calibrating current type i e type 06 07 and 1A the jumper of the corresponding channel should be short Refer to the link for details ftp ftp omega com public DAS...

Page 117: ...V Type Code 09 Input Range 5V 5 V Step 6 Send the zero calibration command Double click on address 831 to set it as ON If the calibration is successful the value will return 0 Step 7 Apply the span ca...

Page 118: ...d the span calibration command Double click on address 832 to set it as ON If the calibration is successful the value will return 0 Step 9 Disable calibration As figure above double click on address 8...

Page 119: ...t directly support type code 0E 19 for AI calibration so you need to change the channel 0 as range 00 02 to complete the work refer to section 5 1 step 3 Step 1 Warm up the module for latest 30 minute...

Page 120: ...f ch1 1 run W Pulse 00834 1 Span calibration command of ch1 1 run W Pulse 00835 1 Zero calibration command of ch2 1 run W Pulse 00836 1 Span calibration command of ch3 1 run W Pulse 00837 1 Zero calib...

Page 121: ...calibration Step 4 Connect the zero calibration resistor Refer to the table Type Code Step 5 Send the zero calibration command Refer to the table Modbus Address for Calibration Step 6 Connect the spa...

Page 122: ...ibration to Factory Setting Please go to the configuration page of Modules I O Settings Analog Input refer to Section 3 2 3 After you selecting the Recover AI Calibration to Factory Setting it will au...

Page 123: ...talled on your system installation of the MiniOS7 Utility should be the first step Please refer to section 2 4 Installing the MiniOS7 Utility to install it 6 1 Establishing a Connection To upload firm...

Page 124: ...niOS7 modules on your network Step 3 Click the IP address in the IP Port field list and then click the Connect icon in the toolbar After the search has been completed click the IP address for the OME...

Page 125: ...nection symbol to make sure that the connection is established A connection symbol Check the connection symbol status in the top right side to make sure the connection has been established Connection...

Page 126: ...change protocols to support them Step 1 Establish a connection to the OME ET 7000 OME PET 7000 For a more detailed description of this instruction please refer to section 6 1 Establishing a Connection...

Page 127: ...he Confirm dialog will appear and then click Yes button to continue and stop the firmware running Step 4 Click Yes to continue After confirming the command the Confirm dialog will appear and then clic...

Page 128: ...e so we advise you to periodically check with OMEGA web site for the latest updates Step 1 Download the latest version of the MiniOS7 OS image The latest version of the MiniOS7 OS image can be obtaine...

Page 129: ...ing a Connection Step 4 Choose Update MiniOS7 Image from the File menu Choose Update MiniOS7 Image from File menu to start the update procedure Step 5 Select the latest version of the MiniOS7 OS image...

Page 130: ...just need to wait awhile until the following dialog appear and then click OK button to finish the procedure Step 7 Press F7 or choose Info from the Command menu to check the OS version After pressing...

Page 131: ...advise you to periodically check the ICP DAS web site for the latest updates Step 1 Download the latest version of the firmware ET 7000 The latest version of the MiniOS7 OS image can be obtained from...

Page 132: ...h is set to the Init position and then reboot the module Step 3 Establish a connection to connection to the OME ET 7000 OME PET 7000 For a more detailed description of this instruction please refer to...

Page 133: ...establishing a connection then choose Erase Disk from Command menu or right click on the right of window to erase the contents of the flash memory Tips Warnings You have to delete all files existed o...

Page 134: ...ng the Erase Disk command the Confirm dialog will appear and then click Yes button to continue erasing the memory contents Step 6 Select the latest version of the firmware Upload the last version of t...

Page 135: ...the module After confirming the command you just need to wait awhile until the following dialog appear and then click OK button to finish the procedure After the update is completed set the switch on...

Page 136: ...rawback is that there are no visual indications of the configuration of the module New OME ET 7000 OME PET 7000 modules include node information areas that are protected by a cover as shown below and...

Page 137: ...rtional to the temperature This implies that the temperature reading can be obtained by measuring the emf We cannot measure the emf V1 directly because when a voltmeter is connected to the thermocoupl...

Page 138: ...The Host Watchdog is a software function that can be used to monitor the operating status of the host Its purpose is to prevent network communication problems or a host failure If the Watchdog timeout...

Page 139: ...output modules under 3 conditions power on reset by Module Watchdog reset by the reset command User can set the power on value of the specific analog digital output channel and the power on value is...

Page 140: ...00 OME PET 7000 web page and then click the Module I O Settings option in the Configuration section of the Main Menu Step 2 Set the Power on Value in the Power on Value text box Step 3 Click the Submi...

Page 141: ...ices By default this feature is disabled User can enable this feature by configuring the Host WDT Timeout Setting the Safe Value for a Specific Digital Output Channel Step 1 Log into the OME ET 7000 O...

Page 142: ...T 7000 OME PET 7000 web page and then click the Module I O Settings option in the Configuration section of the Main Menu Step 2 Set the Safe Value in the Safe Value text box Step 3 Click the Submit bu...

Page 143: ...igh Low Alarm Switch Table Channel Number AI High Alarm AI Low Alarm Register Description Register Description AI0 00636 0 Disable 1 Enable 00668 0 Disable 1 Enable AI1 00637 0 Disable 1 Enable 00669...

Page 144: ...igh Alarm Value of AI Low Alarm Value of AI Register Description Register Description AI0 40296 32768 32767 40328 32768 32767 AI1 40297 32768 32767 40329 32768 32767 AI2 40298 32768 32767 40330 32768...

Page 145: ...on AI0 00700 0 Momentary Mode 1 Latch Mode 00732 0 Momentary Mode 1 Latch Mode AI1 00701 0 Momentary Mode 1 Latch Mode 00733 0 Momentary Mode 1 Latch Mode AI2 00702 0 Momentary Mode 1 Latch Mode 00734...

Page 146: ...arm occurred the value of register is 1 In normal condition it will be 0 Latch Alarm When the Latch Alarm mode is enabled the register stays latched until the specified registers are cleared For examp...

Page 147: ...OME ET 7000 OME PET 7000 web page and then click the Module I O Settings option in the Configuration section of the Main Menu Step 2 Set the High Alarm and Low Alarm information in the relevant field...

Page 148: ...uts and stays the value until another minimum input enters Monitoring the Alarm Status for a Specific Analog Input Channel Click the Web HMI link in the Web HMI Section of the Main Menu tree Step 1 Lo...

Page 149: ...0000 2 s comp HEX 7FFF 8000 03 500 500 mV Engineering Unit 5000 5000 2 s comp HEX 7FFF 8000 04 1 1 V Engineering Unit 10000 10000 2 s comp HEX 7FFF 8000 05 2 5 2 5 V Engineering Unit 25000 25000 2 s c...

Page 150: ...nit 20000 0 2 s comp HEX FFFF 0000 0E Type J Thermocouple 210 760 C Engineering Unit 7600 2100 2 s comp HEX 7FFF DCA2 0F Type K Thermocouple 270 1372 C Engineering Unit 13720 2700 2 s comp HEX 7FFF E6...

Page 151: ...Unit 8000 2000 2 s comp HEX 7FFF E000 18 Type M Thermocouple 200 100 C Engineering Unit 10000 20000 2 s comp HEX 4000 8000 19 Type L DIN43710 Thermocouple 200 900 C Engineering Unit 9000 2000 2 s com...

Page 152: ...3916 0 600 C Engineering Unit 6000 0 2 s comp HEX 7FFF 0000 28 Nickel 120 80 100 C Engineering Unit 10000 8000 2 s comp HEX 7FFF 999A 29 Nickel 120 0 100 C Engineering Unit 10000 0 2 s comp HEX 7FFF 0...

Page 153: ...00 C Engineering Unit 20000 20000 2 s comp HEX 7FFF 8000 80 Platinum 100 0 00385 200 600 C Engineering Unit 6000 2000 2 s comp HEX 7FFF D556 81 Platinum 100 0 003916 200 600 C Engineering Unit 6000 20...

Page 154: ...20000 0 2 s comp HEX FFFF 0000 31 4 20 mV Engineering Unit 20000 4000 2 s comp HEX FFFF 0000 32 0 10 V Engineering Unit 10000 0 2 s comp HEX 7FFF 0000 33 10 10 V Engineering Unit 10000 10000 2 s comp...

Page 155: ...llows a single device such as a router to act as an agent between the Internet or public network and a local or private network This means that only a single unique IP address is required to represent...

Page 156: ...ateway must be set to the IP address of router i e 10 1 0 1 Step 2 Connect to the web server of OME ET 7000 OME PET 7000 module with the public IP address on the Internet For accessing the web page th...

Page 157: ...restricted by the IP filter settings Check the IP filter setting using the Web configuration There are more than 30 TCP IP connections Reboot the module Able to explore the web page through Port 80 u...

Page 158: ......

Page 159: ......