36 (48)
RE03 1406 EN
32
Flow sensor 2
BX21
No measurement
from outgoing water
Check Heating Circuit 2
flow sensor connection.
33
Flow sensor HP
BX10
No measurement
from outgoing water
Check Heating Circuit P
flow sensor connection.
35
Source inlet sensor
BX13
No measurement
from source inlet
sensor
Check source inlet sensor.
36
Hot-gas sensor 1
BX7
No measurement
from hot gas sensor
Check hot gas sensor
measurement connection.
40
Condenser difference
max.limit
Too high
temperature over
condenser
Check heating circuit
venting.
Increase pump rotation
speed.
41
Condenser difference
min.limit
Too low temperature
over condenser
Slow down pump rotation
speed.
42
Evaporator difference
max. limit
Too large
temperature
difference over
evaporator
Check ground circuit
venting.
Increase pump rotation
speed.
Check screen.
43
Evaporator difference
min. limit
Too small
temperature
difference over
evaporator
Check compressor
operation.
106 Source temp too low
Too low ground
circuit temperature
Vent ground circuit.
Check that pump rotation
speed is at maximum.
107 Hot-gas compressor 1
Compressor hot gas
temperature too high
Check:
● collector circuit
temperature
● condensation
temperature
● expansion valve
setting
222 High-press in HC
operation
E10
Compressor has
reached maximum
pressure at pressure
side
Adjust maximum
temperature for outgoing
water lower.
223 High-press on start
HC
E10
Compressor
has reached
overpressure at HC
circuit start-up
Check that condenser
pump is operational.
Check screen.
224 High-press on start
DHW
E10
Compressor
has reached
overpressure at
DHW heating start-
up
Check that condenser
pump is operational.
Summary of Contents for RE 110
Page 2: ......
Page 45: ...RE03 1406 EN 43 48 WIPL02 ver 1 Figure1 Wilo IPL 50 115 0 75 2...
Page 46: ...44 48 RE03 1406 EN WIPL01 ver 1 Figure2 Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2...
Page 47: ...RE03 1406 EN 45 48 WSP03 ver 1 Figure3 Wilo Stratos Para 25 1 7...
Page 51: ......
Page 52: ...www oilon com...