RE03 1406 EN
39 (48)
6. Technical data
6.1. Technical data
Dimensions and weight
RE 110
RE 140
RE 170
Height (mm)
1798
1798
1798
Width (mm)
1746
1746
1746
Depth (mm)
863
863
863
Weight (kg)
800
900
1000
Connections
RE 110 – RE 170
Ground circuit return/out
G 2 1/2 (external thread)
Water to/from condenser
G 2 1/2 (external thread)
Water to/from desuperheater
(optional)
G 1 1/4 (external thread)
Electrical data
RE 110
RE 140
RE 170
Electrical connections
3 / N / PE 400 V 50 Hz
Compressor start-up current (A)
211
248
319
Compressor maximum operating
current (A)
2 x 50
2 x 64
2 x 78
Fuse size (A)
125
160
200
Refrigerant circuit
RE 110
RE 140
RE 170
Refrigerant
R410A
R410A
R410A
Refrigerant (kg)
(without desuperheater)
2 x 11
2 x 13
2 x 15.5
The amount of the refrigerant varies depending on the optional
equipment integrated into the heat pump.
Always when carrying out maintenance tasks check the exact
amount of the refrigerant from the heat pump’s identification
plate.
Summary of Contents for RE 110
Page 2: ......
Page 45: ...RE03 1406 EN 43 48 WIPL02 ver 1 Figure1 Wilo IPL 50 115 0 75 2...
Page 46: ...44 48 RE03 1406 EN WIPL01 ver 1 Figure2 Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2...
Page 47: ...RE03 1406 EN 45 48 WSP03 ver 1 Figure3 Wilo Stratos Para 25 1 7...
Page 51: ......
Page 52: ...www oilon com...