225 Low pressure
E9
Compressor intake
pressure is below
low pressure
minimum limit
Check that ground
circulation pump is
rotating.
Check ground circuit and
well, vent if necessary.
Check that ground
circulation pump rotation
speed is at maximum.
226 Compressor 1
overloaded
E11
Compressor
overloaded
Compressor soft-starter
is broken or compressor’s
OCS-protection device
have stopped the
compressor. You can try
reset the alarm and check
if the compressor starts.
If failure continues, call
service.
227 Compressor 2
overloaded
E11
Compressor
overloaded
Compressor soft-starter
is broken or compressor’s
OCS-protection device
have stopped the
compressor. You can try
reset the alarm and check
if the compressor starts.
If failure continues, call
service.
324 BX same sensors
BX-outputs
connected using
same address
Change sensor
addresses.
325 BX/e', same sensors
BX/e'module same
sensors
Change sensor
addresses.
327 E’module same funct.
Same function for
additional modules
Check added module
operation.
329 E’mod/m’grp same
funct.
Same function for
mixing groups
Check added mixing
group operation.
5.4. Compressor protection device
Both compressors, are equipped with operating control system (OCS) devices. The
OCS device controls the temperature and pressure of the compressor and with liquid
injection valve (LIV) keeps those in optimal level for the heat pump’s compressor. The
OCS device provides also a protection system for the compressor. The OCS device is
connected to:
● discharge gas temperature sensor
● low pressure and high pressure transmitters
● phase monitoring.
Only Oilon expert is allowed to check and carry out maintenance
tasks for OCS device.
Summary of Contents for RE 110
Page 2: ......
Page 45: ...RE03 1406 EN 43 48 WIPL02 ver 1 Figure1 Wilo IPL 50 115 0 75 2...
Page 46: ...44 48 RE03 1406 EN WIPL01 ver 1 Figure2 Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2...
Page 47: ...RE03 1406 EN 45 48 WSP03 ver 1 Figure3 Wilo Stratos Para 25 1 7...
Page 51: ......
Page 52: ...www oilon com...