32 (48)
RE03 1406 EN
Heat pump
Operating line number
Function
2880
Use electric flow
Setting for switching on electric heater. Options:
● Substitute: Electric heater is used only in failure
mode.
● Complem operation HC: If heat pump cannot
produce required capacity for heating circuit,
electric heater is switched on after delay and
after integral has been reached.
● Complem operation DHW: If heat pump cannot
produce required capacity for domestic hot
water heating, electric heater is switched on
after delay and integral has been reached.
● Complem operation HC+DHW: If heat pump
cannot produce required capacity for domestic
hot water or heating circuit, electric heater is
switched on after delay and integral has been
reached.
● Stop domestic hot water heating: When heat
pump reaches high pressure or maximum
temperature during domestic hot water charge,
charging is finished with electric heater.
2881
Locking time electric flow
Time from heat pump start until integral counting
for electric heater release begins.
2884
Release el flow before OT
If electric heater is switched on only at the lowest
outdoor temperatures, set temperature limit for
electric heater to switch on.
If value is set to “---“, electric heater can be
switched on without outside temperature limit.
Configuration
Operating line number
Function
5710
Heating circuit 1
Defines if Heating circuit 1 is in use.
5715
Heating circuit 2
Defines if Heating circuit 2 is in use.
5890, 5891, 5892, 5894, 5895,
5896
Relay output QX1 – QX6
Relays can be set for example for DHW feed
pump, solar panel pump etc. Remember to connect
2A fuse in between, if connected start to controller
without relay.
Summary of Contents for RE 110
Page 2: ......
Page 45: ...RE03 1406 EN 43 48 WIPL02 ver 1 Figure1 Wilo IPL 50 115 0 75 2...
Page 46: ...44 48 RE03 1406 EN WIPL01 ver 1 Figure2 Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2...
Page 47: ...RE03 1406 EN 45 48 WSP03 ver 1 Figure3 Wilo Stratos Para 25 1 7...
Page 51: ......
Page 52: ...www oilon com...