71
Inverter swimming pool heat pump
GB
Forced defrost function
4.14
Parameter table
4.15
Press
and the arrow button for 3 seconds to enter the forced defrosting function.
P01
Temperature deviation setting for restart
1 ~ 18 °C
1 °C
P02
Reserved
—
—
P03
Reserved
—
—
P04
Cooling temperature setting
8 ~ 28 °C
27 °C
P05
Heating temperature setting
15 ~ 40 °C
27 °C
P06
Protection against excessive discharge gas
temperature
80 ~ 125 °C
120 °C
P07
Reset temperature for excessive discharge gas
temperature
50 ~ 100 °C
95 °C
P08
Protection compressor current
2 ~ 50 A
Reserved
P09
Compensation coeffi cient setting of water
supply temperature
-5 ~ 15 °C
0 °C
P10
Reserved
—
—
P11
Auto activation time before defrosting starts
20 ~ 90 min
45 min
P12
Temperature for activation of defrosting
function
-15 ~ -1 °C
-3 °C
P13
Maximum duration of defrosting
5 ~ 20 min
8 min
P14
Temperature for deactivation of defrosting
function
1 ~ 40 °C
20 °C
P15
Temperature diff erence between ambient
air temperature and coil temperature during
defrosting
0 ~ 15 °C
2 °C
P16
Ambient temperature during defrosting
0 ~ 20 °C
17 °C
P17
Active period of expansion valve
20 ~ 90 s
45 s
P18
Target overheat temperature during heating
-5 ~ 10 °C
1 °C
P19
EEV setting of discharge gas temperature
70 ~ 125 °C
95 °C
P20
EEV opening
20 ~ 450
300
P21
Mini opening for electronic expansion valve
50 ~150
80
P22
EEV operating principle
0= annual / 1= auto
1
P23
EEV annual step
20 ~ 450
350
P24
Target overheat temperature during cooling
-5 ~ 10 °C
3 °C
P25
Switch-off time of pump after reaching set
temperature
1 ~ 99 min
45 min
P26
Working time of pump after reaching set time
1 ~ 99 min
5 min
P27
EEV operating principle during cooling
0=environment /
1=overheat temperature
1
P28
Servo-control mode fi ltration pump
0=stop / 1=operation
1
Code
Description
Setting range
Default setting
* Parameter 01 allows for a
modifi cation of the temperature
deviation compared to the tar-
get temperature, which causes
the heat pump to restart.
Example: Assuming, the para-
meter value 01 is 1 °C. After
reaching the target temperature
(e.g. 27 °C), the heat pump
restarts as soon as the pool tem-
perature drops to 26 °C (27 – 1).
** Parameter 28: Control mode
of circulation pump. When you
switch on your heat pump, the
circulation pump starts, and
1 minute later the compressor
of the heat pump is activated.
When the heat pump stops,
the compressor and the fan will
shut down. After 30 minutes,
the circulation pump will fol-
low. During a defrost cycle, the
circulation pump will continue
to operate irrespective of the
selected mode.