Special adjustments
Menu stage 9: Special functions
Push button
.
“9” is displayed.
Menu
Operating mode
value
0
Normal operation (factory setting upon delivery)
1
Normal operation with ventilation position
2
Partial opening of side sectional door
A partial opening is affected by means of a 180-Ohm resistance
at the starting input.
5
Operation with single-lane control
(only along with traffic light control)
An external photcell safety device is required.
6
Automatic Closing
An external photocell safety device is required.
Set open phase in menu stage A.
7
Automatic Closing
Termination of the open phase via light barrier
8
Automatic Closing
Termination of the open phase via impulse generator
For a description of the function, please refer to the Operating Instructions.
Note:
With all special functions, the “4-minute light” function is deleted the next
time the power supply is interrupted.
Regarding double-leaf doors, the travel direction has to be changed in menu
stage 3.
Menu stage “A”: Open phases of the door
Press button
.
“A” is displayed. These phases can only be set using the menu values 6/7/8
under menu stage “9”.
Menu
Open phase (without warning time 10 seconds)
value
0
0 s
1
10 s
2
30 s
3
60 s
4
90 s
5
120 s
6
150 s
7
180 s
8
210 s
9
240 s
Connection terminals motor head
All terminals as described under point 13, but with the following special functions:
G “STOP A” input - When adjusting “side sectional door” (menu stage 9 - 3/4)
terminal for external pulse generator “partial opening”
N CLOSE status signal output
connection to traffic light control, potential-free relay
120 V AC /0.5 A or 24 V DC /1A
M OPEN status signal output
Connection to traffic light control, potential-free relay
120 V AD /0.5 A or 24 V DC /1 A
L output for connection of stairway automation, potential-free relay,
250 V AC /5A
Relaiskontakt, 250 V AC /5A
F In operating mode1 and 2, the input can cause the function air ventilation
position or
partial opening by connecting a 180-Ohm resistance.
Terminal traffic light control
T - Traffic light control
J - receiver module
Unplug the receiver module from the operator and insert it into traffic light
Control.
22
22a
23
G
H
I
J
F E
230V
24V
˜
˜
K
M N
L
G
H
I
J
F E
K
M N
L
T
23
22