2.1. META Section 

It  contains  the  general  information  about  the  file  and  settings  for  its  execution,  and  is  responsible  for  the 

particularities of the program cycle fulfillment (the so-called "updates"), including the frequency of updates. Lines in 
it do not have numbering, instead of index is "*". Each line has the following format:  

 

* <modifier type> <argument>

 

 

The types of the arguments are the following: 

 

<int>

 - 32-bit signed integer

 

 

<uchar>

 - 8-bit unsigned integer

 

 

<ushort>

 - 16-bit unsigned integer

 

Table C.2 

 

Types of modifiers 

PROTOCOLVERSION 

<int> 

Version of the file

: It prevents the processing of files with outdated firmware EM-481. 

The version described in this document is 8.

 

UPDATE

 <int> 

Frequency of the program cycle fulfillment (update rate) in seconds

: Every cycle 

has  the  reading  of  parameters,  calculation  of  variables  values,  defining  operation 
conditions  and  implementation  of  response  to  these  conditions.  The  frequency 
determines only the approximate time of the cycle restart. If during the task execution 
the time of the new update (this or another task) will be skipped, this new update will 
be postponed

 

until the end of the running cycle. If one or more updates are missed for 

the  deferred  update,  these  additional  updates  will  not  be  performed.  The  minimum 
value is 1 second.

 

UPDATEDIVISOR modifier should be used for the higher speeds.  

By default, if a modifier is not specified, it equals to 60. 

UPDATEDIVISOR 
<int> 

Updating  rate  divisor  allows 

you  to  speed  up  the  updating  rate.  If  the  divisor  is  0, 

update  cycles  are  performed  with  an  accuracy  of  not  more  than  1  second.  For  other 
values, the accuracy is not more than 0.002 s, with the resulting frequency equal to the 
value of the UPDATE / UPDATE DIVISOR fraction, cannot be more than 60 s or less 
than  0.002  s.  Practical  limiting  speed,  as  a  rule,  is  less.  The  speed  is  significantly 
reduced when using SMS and parameters in the task file, which are accessed through 
RS-485 and GSM interfaces. 
By default, if no modifier is specified, it is 0.

 

PARAMACTUAL

 

<ushort> 

Frequency of reading the parameters in seconds

: It allows optimizing the number of 

readings  of  parameters.  At  the  moment  of  the  updating  the  parameter  it  is  checked 
how many seconds ago it was read last time, and if this time is not more than the value 
PARAMACTUAL,  then  upgrade  option  will  not  be  read  and  the  last  read  value  of  the 
parameter  will  be  accepted  as  current  one.  Thus,  if  the  total  program  consists  of 
several  files,  reading  the  same  parameters,  the  number  of  readings  of  these 
parameters and the excessive load on the communication channels can be reduced. 
For the value 0 

– with each update the parameter values will be read again. 

By default, if a modifier is not specified, it equals to 0. 

PARAMRETRIES 

<uchar> 

Number  of  times  to  repeat  reading  in  case  of  error

:  The  value  0  for  the 

programming cycle there will not be more than one attempt to read the parameter. For 

–  it  will  be  made  up  to  two  attempts  to  read,  etc.  Calculations  and  reaction  to 

conditions  can  be  performed  even  without  a  successful  reading  of  all  parameters,  if 
they have sufficient known data. 
By default, if a modifier is not specified, it equals to 0. 

PARAMTIMEOUT

 

<int>  

Time of waiting for response to MODBUS query in milliseconds

: It is used if in the 

settings of EM-481 the total timeout MODBUS is more than frequency of update of this 
file, or if the exception code generation is disabled if no MODBUS response. 
By default, if a modifier is not specified, it equals to 1000. 

PARAMLOADRATIO 

<uchar> 

Maximum  load  of  RS-485  channel,  in  percent

:  After  each  query  a  delay  is  added, 

depending  on  the  waiting  time  of  the  last  response  that  allows  other  clients  to  send 
queries and receive responses. A value of 100 generates the minimum possible delays 
(it is not recommended). A value of 50 means a delay equal to the time of waiting for a 
response. A value of 25 means a delay of 3 times exceeding the response time. 
By default, if a modifier is not specified, it equals to 25. 

Summary of Contents for EM-481

Page 1: ...development and production complies with the requirements of ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device...

Page 2: ...d via RS 485 9 5 2 2 3 Access to MODBUS network using MODBUS TCP 9 5 2 2 4 Access to MODBUS network using SMS 9 5 2 2 5 Data collection and event tracking 10 5 3 Configuration 10 5 3 1 General 10 5 3...

Page 3: ...THE HOUSING IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE DEVICE During operation and maintenance the regulatory document requirements must be met namely Regulations fo...

Page 4: ...ing and transferring data IP protocol is routable protocol for transferring data by Ethernet It is a part of TCP IP and used for Internet IP address is a node address which is unique within a single n...

Page 5: ...showing of warnings about detected faults 4 GSM LED is blinking every 3 sec when there is connection via GSM network or UMTS it is blinking 3 times per second while data exchanging via GPRS or HSPA 5...

Page 6: ...ort circuit output voltage of driver RS 485 maximum mA 250 Resistance of in built terminator Ohm 1000 The recommended number of connected devices in Modbus network when the input current of receivers...

Page 7: ...vice operation Check the device for damage after transportation in case of such damages detection contact the supplier or the manufacturer Carefully study the Operating Manual pay special attention to...

Page 8: ...in the SIM slot and connect the GSM antenna to the ANT connector SMA F connector 5 2 Using the device 5 2 1 General After power is turned on all indicators except LAN and GSM light up and EM 481 perf...

Page 9: ...addresses identifiers If the query could not be redirected for example in the RS 485 slave mode if the connection to the remote MODBUS TCP server was terminated the EM 481 can generate and send the MO...

Page 10: ...ters of address in Ethernet network if Ethernet is used and server address to which EM 481 is connected automatically The adjustable parameters are described in items 5 3 2 The parameters remain saved...

Page 11: ...ess MAC 48 from left to right 6 Table 5 5 Parameters describing the device Parameter Description Address Device type The code that defines the MODBUS product by the manufacturer 23 EM 481 0 Firmware v...

Page 12: ...d access tabs 0 no permission 1 there is permission Bit 6 It is always as 1 Bit 7 Permission for the connected client to configure EM 481 the same as register 121 0 no permission 1 there is permission...

Page 13: ...on to remote server Modbus TCP 0 connection to the remote server is set 1 connecting to the remote server 2 65534 the number of seconds before reconnecting 65535 Connection to the Modbus TCP server is...

Page 14: ...parameters Parameter Range of values Factory setting Description Address Ethernet network Static IP address IP address 192 168 0 111 If the dynamic addressing is switched off or not available IP addre...

Page 15: ...vice provider up to 24 characters 392 415 APN address of host Character string Provided by the GSM service provider up to 34 characters there cannot be spaces in a string 416 449 MODBUS TCP clients Co...

Page 16: ...tart bit 7 data bits 2 stop bits or parity bit and stop bit total is 10 bits The non standard byte formats register 461 values 4 and 5 are not available in this case format 3 2 stop bits is used inste...

Page 17: ...ssword This string should not have any spaces 540 549 The specified password for recording per mission via MODBUS TCP in devices using RS 485 Character string It is used to access devices connected to...

Page 18: ...Gateway Path Unavailable response is not returned to the client 1 255 if there is no connection to the query addressee this exception code is returned to the client 636 Enable RS 485 slave mode 0 1 0...

Page 19: ...aylight saving time 1 10 10 It is used if you selected the automatic transition to daylight saving time on the specified days Week of the month when the clock will be set one hour ahead 1 5 week of th...

Page 20: ...f clock for synchroniza tion s 1 180 2 It is used if you have enabled synchronization of clocks with the server clock The synchronization is performed after receiving the server time if the difference...

Page 21: ...ears once again 5 3 4 EM 481 configuring via MODBUS interface Setting via Modbus interface shall be provided if the device is connected using the Modbus client which is supporting the Modbus TCP proto...

Page 22: ...return and transfer it to the warranty post warranty service please indicate detailed reason for the return in the field of the claims data 8 TRANSPORTATION AND STORAGE The device in the original pack...

Page 23: ...in the GSM network is displayed alternately with the IP address in the local Ethernet network The operation speed with remote Modbus TCP server is improved The speed of GSM operation is increased 30...

Page 24: ...481 Parameter Value Addressing using DHCP Yes IP address 192 168 0 111 Subnet mask 255 255 255 0 Gateway 192 168 0 1 With the factory settings of the EM 481 two ways are possible for communicating wi...

Page 25: ...ter closing the windows answer yes 3 Connection to Internet via Ethernet ATTENTION THE USER IS STRONGLY RECOMMENDED TO CONNECT THE UNIT TO INTERNET UNDER THE SUPERVISION OF THE LAN SYSTEM ADMINISTRATO...

Page 26: ...om the client over the long period the access returns to locked mode ATTENTION DURING ANY CONNECTIONS EXCEPT FOR TRANSMITTING VIA GSM AND COMMUNICATION WITH SERVER VIA SPECIAL PROTOCOL EM 481 THE PASS...

Page 27: ...age in order to delete the device from Overvis system That guarantees that the EM 481 device will be used only by the authorized users Using the instruction on the site of Overvis system connect to EM...

Page 28: ...again the internal memory to re read the program Files can have arbitrary names and extensions and placed in subfolders of the folder TASKS Files placed directly in the folder TASKS allow you to use...

Page 29: ...s The file can contain comment lines that begin with and are ignored when reading the file Correct example Incorrect example This is a comment VARS number of seconds per minute 0 VAL 60 1 VAL 1 This i...

Page 30: ...eters in the task file which are accessed through RS 485 and GSM interfaces By default if no modifier is specified it is 0 PARAMACTUAL ushort Frequency of reading the parameters in seconds It allows o...

Page 31: ...in a single query WRHMULTIPLE uchar uchar Device can write only using function 16 in the storage registers The first argument specifies how many registers can be read in one query the second one deter...

Page 32: ...point 100 F32BLEEP3R 32 bit with reverse order of bytes and floating point 1000 F32WLEEP0R 32 bit with reverse order of words and floating point F32WLEEP1R 32 bit with reverse order of words and floa...

Page 33: ...all variables in the specified range VARSMINIDX var ref var ref The number of the minimum variable in the specified range VARSMAX var ref var ref Maximum of all variables in the specified range VARSMA...

Page 34: ...ref Copy of the condition CONDIS int Set to the specified value The condition is met if the value is not 0 It can be used for adjustment or for unconditional actions for each update cycle NOT cond ref...

Page 35: ...has the following format index action type argument 1 argument 2 Index the sequential number of the line The types of the arguments int 32 bit signed integer alarm reason is the number of reason of t...

Page 36: ...n the text 3 MODBUS ID of the device is OM 310 240 is the register address which is monitored for the fault enabling relay 1 depending on bit 0 of register 240 of device 3 META 8th version of Protocol...

Page 37: ...hieving the temperature respectively the lower or upper limits These registers are read only To change them you should be in configuration mode see it 5 3 4 then write the desired values to addresses...

Page 38: ...VARGEVAR V2 V1 in other cases do not change the hysteresis current value 2 CONDIS 1 VARS the desired hysteresis is selected from V3 V5 according to the conditions of C0 C2 6 VARSSELBYC V3 C0 CONDS is...

Page 39: ...ting select the file of updating The procedure for file selection is given in Table D 2 To cancel the updating cut off the power supply of EM 481 or wait until automatic completion of updating mode Ta...

Page 40: ...Similar to No 2 but the file with an error has less priority The error is automatically corrected with available files of updating 4 The files of updating are not available Escape from the mode of upd...

Reviews: