background image

-

 31

 - 

NOVATEK-ELECTRO                                                                                                                                  EM-481

                                                                                                                                                             

 

Example: 

!META

 

* PROTOCOLVERSION 8

 

* UPDATE 5 
* PARAMRETRIES 2 

 

2.2. DEVICES Section 

It  contains  the  capabilities  of  MODBUS  devices,  the  settings  of  not  specified  here  devices  will  be  treated  the 

same  as  for  the  device  with  maximum  features  and  functions.  The  lines  in  this  section  do  not  have  numbering, 
instead of 

an index is “*”. Each line has the following format: 

 

* <MODBUS ID of device> <record type> <argument 1> [argument 2]

 

 

MODBUS  device  ID:  a  number  from  1  to  247.  “0”  –  is  the  broadcast,  it  can  be  used  to  configure  recording 

simultaneously to all devices that support the broadcasting (the argument 1 in this case is defined, but not used). "*" 
instead  of  the  MODBUS  ID  means  a  device  by  default  for  this  folder  (EM-481,  if  the  file  is  placed  directly  in  the 
program folder,  or  device  with  the  MODBUS  ID  of  the  name  of  the  subfolder,  if  the  file is  placed  in  the  subfolder 
named "1" to "247"). 

Lines with different types or arguments, but with the same MODBUS ID are not permitted. These lines being in 

different files in the folder of programs are also considered to be incorrect. 

Arguments type

<uchar>

 

– 8-bit unsigned integer. 

Table C.3

 

– Types of records 

WRHANY

 <uchar> 

<uchar> 

Device  can  write  both  as  a  function  of  6  and  function  of  16  in  the  storage 
registers

.  The  first  argument  specifies  how  many  registers  can  be  read  in  one  query; 

the second one determines how many you can record in a single query. 

WRHMULTIPLE

 

<uchar> <uchar> 

Device can write only using function 16 in the storage registers

. The first argument 

specifies how many registers can be read in one query; the second one determines how 
many you can record in a single query. 

WRHSINGLE

 <uchar> 

Device can write only using function 6 in the single storage register

. The argument 

specifies how many registers can be read in one query. 

WRHDENIED 

<uchar> 

Device  can't  write  to  the  storage  registers

.  The  argument  specifies  how  many 

registers can be read in one query. 

Example: 

!DEVICES

 

* * WRHANY 50 50

 

* 3 WRHSINGLE 4

 

 
2.3. PARAMS Section 

It  contains  parameters,  their  addressing,  and  conversion  between  types  (how  they  are  used  by  the  device). 

When reading the settings are always converted from the specified type to the default type for the program EM-481 
(INT32 

– 32-bit signed integer). When recording the inverse transform is performed. The lines in this section are in 

ascending order, starting from zero. Each line has the following format: 

 

<index> <MODBUS ID of device> <data type> <register table> <address>

 

 

Index: the sequential number of the line. 

MODBUS ID of device: a number from 1 to 

247. “0” – is the broadcast, it can be used for writing only. "*" instead 

of  the  MODBUS  ID means  a  device by  default for this  folder  (EM-481,  if  the  file  is  placed  directly  in  the  program 
folder, or device with the MODBUS ID of the name of the subfolder, if the file is placed in the subfolder named "1" to 
"247"). 

Tables of registers: 

 

H

 

- storage registers (most frequently used registers) 

 

I

 - input registers; 

 

D

 - digital inputs; 

 

С

 

– tabs. 

Address: a number from 0 to 65535. 

Summary of Contents for EM-481

Page 1: ...development and production complies with the requirements of ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device...

Page 2: ...d via RS 485 9 5 2 2 3 Access to MODBUS network using MODBUS TCP 9 5 2 2 4 Access to MODBUS network using SMS 9 5 2 2 5 Data collection and event tracking 10 5 3 Configuration 10 5 3 1 General 10 5 3...

Page 3: ...THE HOUSING IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE DEVICE During operation and maintenance the regulatory document requirements must be met namely Regulations fo...

Page 4: ...ing and transferring data IP protocol is routable protocol for transferring data by Ethernet It is a part of TCP IP and used for Internet IP address is a node address which is unique within a single n...

Page 5: ...showing of warnings about detected faults 4 GSM LED is blinking every 3 sec when there is connection via GSM network or UMTS it is blinking 3 times per second while data exchanging via GPRS or HSPA 5...

Page 6: ...ort circuit output voltage of driver RS 485 maximum mA 250 Resistance of in built terminator Ohm 1000 The recommended number of connected devices in Modbus network when the input current of receivers...

Page 7: ...vice operation Check the device for damage after transportation in case of such damages detection contact the supplier or the manufacturer Carefully study the Operating Manual pay special attention to...

Page 8: ...in the SIM slot and connect the GSM antenna to the ANT connector SMA F connector 5 2 Using the device 5 2 1 General After power is turned on all indicators except LAN and GSM light up and EM 481 perf...

Page 9: ...addresses identifiers If the query could not be redirected for example in the RS 485 slave mode if the connection to the remote MODBUS TCP server was terminated the EM 481 can generate and send the MO...

Page 10: ...ters of address in Ethernet network if Ethernet is used and server address to which EM 481 is connected automatically The adjustable parameters are described in items 5 3 2 The parameters remain saved...

Page 11: ...ess MAC 48 from left to right 6 Table 5 5 Parameters describing the device Parameter Description Address Device type The code that defines the MODBUS product by the manufacturer 23 EM 481 0 Firmware v...

Page 12: ...d access tabs 0 no permission 1 there is permission Bit 6 It is always as 1 Bit 7 Permission for the connected client to configure EM 481 the same as register 121 0 no permission 1 there is permission...

Page 13: ...on to remote server Modbus TCP 0 connection to the remote server is set 1 connecting to the remote server 2 65534 the number of seconds before reconnecting 65535 Connection to the Modbus TCP server is...

Page 14: ...parameters Parameter Range of values Factory setting Description Address Ethernet network Static IP address IP address 192 168 0 111 If the dynamic addressing is switched off or not available IP addre...

Page 15: ...vice provider up to 24 characters 392 415 APN address of host Character string Provided by the GSM service provider up to 34 characters there cannot be spaces in a string 416 449 MODBUS TCP clients Co...

Page 16: ...tart bit 7 data bits 2 stop bits or parity bit and stop bit total is 10 bits The non standard byte formats register 461 values 4 and 5 are not available in this case format 3 2 stop bits is used inste...

Page 17: ...ssword This string should not have any spaces 540 549 The specified password for recording per mission via MODBUS TCP in devices using RS 485 Character string It is used to access devices connected to...

Page 18: ...Gateway Path Unavailable response is not returned to the client 1 255 if there is no connection to the query addressee this exception code is returned to the client 636 Enable RS 485 slave mode 0 1 0...

Page 19: ...aylight saving time 1 10 10 It is used if you selected the automatic transition to daylight saving time on the specified days Week of the month when the clock will be set one hour ahead 1 5 week of th...

Page 20: ...f clock for synchroniza tion s 1 180 2 It is used if you have enabled synchronization of clocks with the server clock The synchronization is performed after receiving the server time if the difference...

Page 21: ...ears once again 5 3 4 EM 481 configuring via MODBUS interface Setting via Modbus interface shall be provided if the device is connected using the Modbus client which is supporting the Modbus TCP proto...

Page 22: ...return and transfer it to the warranty post warranty service please indicate detailed reason for the return in the field of the claims data 8 TRANSPORTATION AND STORAGE The device in the original pack...

Page 23: ...in the GSM network is displayed alternately with the IP address in the local Ethernet network The operation speed with remote Modbus TCP server is improved The speed of GSM operation is increased 30...

Page 24: ...481 Parameter Value Addressing using DHCP Yes IP address 192 168 0 111 Subnet mask 255 255 255 0 Gateway 192 168 0 1 With the factory settings of the EM 481 two ways are possible for communicating wi...

Page 25: ...ter closing the windows answer yes 3 Connection to Internet via Ethernet ATTENTION THE USER IS STRONGLY RECOMMENDED TO CONNECT THE UNIT TO INTERNET UNDER THE SUPERVISION OF THE LAN SYSTEM ADMINISTRATO...

Page 26: ...om the client over the long period the access returns to locked mode ATTENTION DURING ANY CONNECTIONS EXCEPT FOR TRANSMITTING VIA GSM AND COMMUNICATION WITH SERVER VIA SPECIAL PROTOCOL EM 481 THE PASS...

Page 27: ...age in order to delete the device from Overvis system That guarantees that the EM 481 device will be used only by the authorized users Using the instruction on the site of Overvis system connect to EM...

Page 28: ...again the internal memory to re read the program Files can have arbitrary names and extensions and placed in subfolders of the folder TASKS Files placed directly in the folder TASKS allow you to use...

Page 29: ...s The file can contain comment lines that begin with and are ignored when reading the file Correct example Incorrect example This is a comment VARS number of seconds per minute 0 VAL 60 1 VAL 1 This i...

Page 30: ...eters in the task file which are accessed through RS 485 and GSM interfaces By default if no modifier is specified it is 0 PARAMACTUAL ushort Frequency of reading the parameters in seconds It allows o...

Page 31: ...in a single query WRHMULTIPLE uchar uchar Device can write only using function 16 in the storage registers The first argument specifies how many registers can be read in one query the second one deter...

Page 32: ...point 100 F32BLEEP3R 32 bit with reverse order of bytes and floating point 1000 F32WLEEP0R 32 bit with reverse order of words and floating point F32WLEEP1R 32 bit with reverse order of words and floa...

Page 33: ...all variables in the specified range VARSMINIDX var ref var ref The number of the minimum variable in the specified range VARSMAX var ref var ref Maximum of all variables in the specified range VARSMA...

Page 34: ...ref Copy of the condition CONDIS int Set to the specified value The condition is met if the value is not 0 It can be used for adjustment or for unconditional actions for each update cycle NOT cond ref...

Page 35: ...has the following format index action type argument 1 argument 2 Index the sequential number of the line The types of the arguments int 32 bit signed integer alarm reason is the number of reason of t...

Page 36: ...n the text 3 MODBUS ID of the device is OM 310 240 is the register address which is monitored for the fault enabling relay 1 depending on bit 0 of register 240 of device 3 META 8th version of Protocol...

Page 37: ...hieving the temperature respectively the lower or upper limits These registers are read only To change them you should be in configuration mode see it 5 3 4 then write the desired values to addresses...

Page 38: ...VARGEVAR V2 V1 in other cases do not change the hysteresis current value 2 CONDIS 1 VARS the desired hysteresis is selected from V3 V5 according to the conditions of C0 C2 6 VARSSELBYC V3 C0 CONDS is...

Page 39: ...ting select the file of updating The procedure for file selection is given in Table D 2 To cancel the updating cut off the power supply of EM 481 or wait until automatic completion of updating mode Ta...

Page 40: ...Similar to No 2 but the file with an error has less priority The error is automatically corrected with available files of updating 4 The files of updating are not available Escape from the mode of upd...

Reviews: