Table 5.8 Continued
Parameter
Range of
values
Factory
setting
Description
Address
Calculation of sunrises and sunsets
Sunny day
0
–3
1
0
– official;
1
– civil;
2
– marine;
3
– astronomical;
709
Latitude,
degree
0
– 89
46
The absolute value of the latitude
710
Latitude,
minute
0
– 59
29
711
Latitude,
second
0
– 59
10
712
Longitude,
degree
0
– 179
30
The absolute value of the longitude
713
Longitude,
minute
0
– 59
43
714
Longitude,
second
0
– 59
40
715
Quadrant
0
– 3
0
0
– N latitude, E longitude;
1
– N latitude, W longitude;
2
– S latitude, E longitude;
3
– S latitude, W longitude;
716
The connection to the server of NTP clock synchronization
NTP server
connection
mode
0
– 4
0
0
– clock synchronization with the server is not used;
1
– to connect to the servers using Ethernet or GPRS, preferably
via Ethernet;
2
– to connect to the servers using Ethernet or GPRS, preferably
via GPRS;
3
– to connect to the servers only via Ethernet;
4
– to connect to the servers only via GPRS;.
717
Time period
of connection
to NTP
servers, h
1
– 240
24
It is used if you have enabled synchronization of clocks with the
server clock. The time interval over which the server time is
received.
718
Minimum shift
of clock for
synchroniza-
tion, s
1
– 180
2
It is used if you have enabled synchronization of clocks with the
server clock. The synchronization is performed after receiving the
server time, if the difference between the clocks is no less than this
value.
719
User settings
User’s
settings and
stored values
0
– 65535
0
They can be used to store any identification data of the device or
for adjusting the settings of task files operation.
5250
–
5499
Setting the clock*
Adding day-
light saving
time, 15 min
-48
– +48
Current gain. It is set during manual transition to the daylight saving
time, when selecting the automatic mode it will be adjusted within 5
minutes
34817
Adding time
zone, 15 min
-48
– +48
8
It is used during synchronization of the clock with the server
clock
34818
Second
0
–59
The time is to be set at the clock
34819
Minute
0
–59
34820
Hour
0
–23
34821
Day
1
–31
34822
Month
1
–12
34823
Year
0
–65534
34824
Set the clock 0
–65535
0
It is used to set the clock. When recording to this register with any
value, the new clock settings in registers 34817-34824 will be set.
34825
*
– registers for the clock setting is available only in the clock setting mode, see registers 120, 122
5.3.3.
EM-481 configuring via WEB-interface
WEB-browser is used for setting via WEB-interface:
1) Write the IP-address of EM-481 in the address bar of the browser (to display the address on the display of