NOVATEK-ELECTRO                                                                                                                                  EM-481

                                                                                                                                                             

 

Parameter 

Range of 

values 

Factory 

setting 

Description 

Address 

MAC-address 
Ethernet set 
manually 

MAC-address 

Unique 

value for 

each device 

It is used when manual MAC-address is enabled to identify 
the device in Ethernet network. 

324 

–  

    329 

GSM network

 

PIN-code of SIM-
card

 

0

–65535 

65535 

– 9999: this code is used for the SIM card if it demands 

the PIN code; 
Other values: the code isn't used, SIM card and GSM are 
unavailable if the card demand a code. 

330

 

Switch on the 
automatic 
detection of APN 
settings 

– 1 

0 - GPRS connection is set according to manually specified 
parameters of APN; 
1 - APN is automatically detected by the GSM pro-vider, in 
accordance with the ICCID code of the SIM card. 

331 

Activate GPRS in 
roaming 

– 1 

0: GPRS is blocked in roaming; 
1: GPRS may be used in roaming; 

332 

Activate SMS in 
roaming  

– 1 

– SMS can be only received in roaming; 

– SMS can be received and sent in roaming; 

 

333 

Connection port 
via MODBUS TCP 
 

– 65535 

It  is  used  for  external  connection  to  the  device  via  GSM  with 
static IP, for communication using the MODBUS TCP protocol. 

– it is disabled. 

334 

Parameter is not 
used 

It is not used; it should be equal to 0 for compatibility. 

  335 

–  

339 

USSD request to 
receive an account 

Character 

string 

 

It is provided by the GSM service provider. Up to 12 
characters. There cannot be any spaces in the line. 

340 

–  

    351 

APN log-in of 
GPRS service 

Character 

string 

 

Provided by the GSM service provider; up to 40 characters;    352 

–  

391 

APN password of 
GPRS service 

Character 

string 

 

Provided by the GSM service provider; up to 24 characters.    392 

–  

415 

APN address of 
host 

Character 

string 

 

Provided by the GSM service provider; up to 34 characters; 
there cannot be spaces in a string; 

  416 

–  

449 

MODBUS TCP clients

 

Connection port 
via MODBUS TCP 

– 65535 

502 

It  is  used  for  external  connection  to  EM-481  for  exchange 
via MODBUS TCP protocol. 

450 

Enable inactive 
clients 
replacement 

– 1 

0:  connection  via  Modbus  TCP  is  supported  regardless  of 

time between queries from client;  

1:  if  all  connections  via  Modbus  TCP  are  used,  a  new  client 

inquiring  for  connection,  can  be  connected  instead  of  a  client 
being inactive for a period which is more than set time   

451 

Max. response 
waiting time, s 

– 600 000 

90 

It is used if the replacement of inactive clients is enabled. 

452 

–  

   453 

Enable the queue 
for the last made 
MODBUS TCP 
connection 

– 1 

0:  connection  via  Modbus  TCP  is  supported  regardless  of 
connection holding time;  
1: If all connections via Modbus TCP are used, a new client 
inquiring for connection can be connected instead of the last 
connected

 

client,

 

if

 

the

 

time

 

of connection

 

holding

 

on

 

is

 

more

 

than

 

the

 

specified time 

454 

Max. time of last 
connection holding 
via Modbus TCP, 
ms 

– 600 000  60 000 

It is used if the queue for the last connection via Modbus 
TCP is enabled 

455 

–  

    456 

MODBUS network

 

 

 

 

Native Modbus- 
identifier of  
EM-481 

– 247 

111 

0 - all queries are sent via MODBUS TCP to the MODBUS 
network, the device registers are unavailable by MODBUS 
TCP; 
1-247 - the device responds MODBUS TCP queries with 
this MODBUS identifier without sending them to the 
MODBUS network. 

457 

Bit rate via  
RS-485, bit/sec 

75 

– 

921 600 

9600 

It is used in case of data exchange between the devices via 
RS-485, the same value for the devices on the same bus-
bar 

458 

– 

   459 

 

Table 5.8 Continued 

Summary of Contents for EM-481

Page 1: ...development and production complies with the requirements of ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device...

Page 2: ...d via RS 485 9 5 2 2 3 Access to MODBUS network using MODBUS TCP 9 5 2 2 4 Access to MODBUS network using SMS 9 5 2 2 5 Data collection and event tracking 10 5 3 Configuration 10 5 3 1 General 10 5 3...

Page 3: ...THE HOUSING IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE DEVICE During operation and maintenance the regulatory document requirements must be met namely Regulations fo...

Page 4: ...ing and transferring data IP protocol is routable protocol for transferring data by Ethernet It is a part of TCP IP and used for Internet IP address is a node address which is unique within a single n...

Page 5: ...showing of warnings about detected faults 4 GSM LED is blinking every 3 sec when there is connection via GSM network or UMTS it is blinking 3 times per second while data exchanging via GPRS or HSPA 5...

Page 6: ...ort circuit output voltage of driver RS 485 maximum mA 250 Resistance of in built terminator Ohm 1000 The recommended number of connected devices in Modbus network when the input current of receivers...

Page 7: ...vice operation Check the device for damage after transportation in case of such damages detection contact the supplier or the manufacturer Carefully study the Operating Manual pay special attention to...

Page 8: ...in the SIM slot and connect the GSM antenna to the ANT connector SMA F connector 5 2 Using the device 5 2 1 General After power is turned on all indicators except LAN and GSM light up and EM 481 perf...

Page 9: ...addresses identifiers If the query could not be redirected for example in the RS 485 slave mode if the connection to the remote MODBUS TCP server was terminated the EM 481 can generate and send the MO...

Page 10: ...ters of address in Ethernet network if Ethernet is used and server address to which EM 481 is connected automatically The adjustable parameters are described in items 5 3 2 The parameters remain saved...

Page 11: ...ess MAC 48 from left to right 6 Table 5 5 Parameters describing the device Parameter Description Address Device type The code that defines the MODBUS product by the manufacturer 23 EM 481 0 Firmware v...

Page 12: ...d access tabs 0 no permission 1 there is permission Bit 6 It is always as 1 Bit 7 Permission for the connected client to configure EM 481 the same as register 121 0 no permission 1 there is permission...

Page 13: ...on to remote server Modbus TCP 0 connection to the remote server is set 1 connecting to the remote server 2 65534 the number of seconds before reconnecting 65535 Connection to the Modbus TCP server is...

Page 14: ...parameters Parameter Range of values Factory setting Description Address Ethernet network Static IP address IP address 192 168 0 111 If the dynamic addressing is switched off or not available IP addre...

Page 15: ...vice provider up to 24 characters 392 415 APN address of host Character string Provided by the GSM service provider up to 34 characters there cannot be spaces in a string 416 449 MODBUS TCP clients Co...

Page 16: ...tart bit 7 data bits 2 stop bits or parity bit and stop bit total is 10 bits The non standard byte formats register 461 values 4 and 5 are not available in this case format 3 2 stop bits is used inste...

Page 17: ...ssword This string should not have any spaces 540 549 The specified password for recording per mission via MODBUS TCP in devices using RS 485 Character string It is used to access devices connected to...

Page 18: ...Gateway Path Unavailable response is not returned to the client 1 255 if there is no connection to the query addressee this exception code is returned to the client 636 Enable RS 485 slave mode 0 1 0...

Page 19: ...aylight saving time 1 10 10 It is used if you selected the automatic transition to daylight saving time on the specified days Week of the month when the clock will be set one hour ahead 1 5 week of th...

Page 20: ...f clock for synchroniza tion s 1 180 2 It is used if you have enabled synchronization of clocks with the server clock The synchronization is performed after receiving the server time if the difference...

Page 21: ...ears once again 5 3 4 EM 481 configuring via MODBUS interface Setting via Modbus interface shall be provided if the device is connected using the Modbus client which is supporting the Modbus TCP proto...

Page 22: ...return and transfer it to the warranty post warranty service please indicate detailed reason for the return in the field of the claims data 8 TRANSPORTATION AND STORAGE The device in the original pack...

Page 23: ...in the GSM network is displayed alternately with the IP address in the local Ethernet network The operation speed with remote Modbus TCP server is improved The speed of GSM operation is increased 30...

Page 24: ...481 Parameter Value Addressing using DHCP Yes IP address 192 168 0 111 Subnet mask 255 255 255 0 Gateway 192 168 0 1 With the factory settings of the EM 481 two ways are possible for communicating wi...

Page 25: ...ter closing the windows answer yes 3 Connection to Internet via Ethernet ATTENTION THE USER IS STRONGLY RECOMMENDED TO CONNECT THE UNIT TO INTERNET UNDER THE SUPERVISION OF THE LAN SYSTEM ADMINISTRATO...

Page 26: ...om the client over the long period the access returns to locked mode ATTENTION DURING ANY CONNECTIONS EXCEPT FOR TRANSMITTING VIA GSM AND COMMUNICATION WITH SERVER VIA SPECIAL PROTOCOL EM 481 THE PASS...

Page 27: ...age in order to delete the device from Overvis system That guarantees that the EM 481 device will be used only by the authorized users Using the instruction on the site of Overvis system connect to EM...

Page 28: ...again the internal memory to re read the program Files can have arbitrary names and extensions and placed in subfolders of the folder TASKS Files placed directly in the folder TASKS allow you to use...

Page 29: ...s The file can contain comment lines that begin with and are ignored when reading the file Correct example Incorrect example This is a comment VARS number of seconds per minute 0 VAL 60 1 VAL 1 This i...

Page 30: ...eters in the task file which are accessed through RS 485 and GSM interfaces By default if no modifier is specified it is 0 PARAMACTUAL ushort Frequency of reading the parameters in seconds It allows o...

Page 31: ...in a single query WRHMULTIPLE uchar uchar Device can write only using function 16 in the storage registers The first argument specifies how many registers can be read in one query the second one deter...

Page 32: ...point 100 F32BLEEP3R 32 bit with reverse order of bytes and floating point 1000 F32WLEEP0R 32 bit with reverse order of words and floating point F32WLEEP1R 32 bit with reverse order of words and floa...

Page 33: ...all variables in the specified range VARSMINIDX var ref var ref The number of the minimum variable in the specified range VARSMAX var ref var ref Maximum of all variables in the specified range VARSMA...

Page 34: ...ref Copy of the condition CONDIS int Set to the specified value The condition is met if the value is not 0 It can be used for adjustment or for unconditional actions for each update cycle NOT cond ref...

Page 35: ...has the following format index action type argument 1 argument 2 Index the sequential number of the line The types of the arguments int 32 bit signed integer alarm reason is the number of reason of t...

Page 36: ...n the text 3 MODBUS ID of the device is OM 310 240 is the register address which is monitored for the fault enabling relay 1 depending on bit 0 of register 240 of device 3 META 8th version of Protocol...

Page 37: ...hieving the temperature respectively the lower or upper limits These registers are read only To change them you should be in configuration mode see it 5 3 4 then write the desired values to addresses...

Page 38: ...VARGEVAR V2 V1 in other cases do not change the hysteresis current value 2 CONDIS 1 VARS the desired hysteresis is selected from V3 V5 according to the conditions of C0 C2 6 VARSSELBYC V3 C0 CONDS is...

Page 39: ...ting select the file of updating The procedure for file selection is given in Table D 2 To cancel the updating cut off the power supply of EM 481 or wait until automatic completion of updating mode Ta...

Page 40: ...Similar to No 2 but the file with an error has less priority The error is automatically corrected with available files of updating 4 The files of updating are not available Escape from the mode of upd...

Reviews: