background image

8

 - 

EM-481 

 

                                                                                                                                                

NOVATEK-ELECTRO

 

  When connecting to the RS-485 bus, use twisted pair cable of category 1 or higher. It is recommended to use 

shielded cable; in this case it should be earthed. 

  When connecting to Ethernet, use the cable supplied, or twisted pair cable of category 5e with 8P8C (RJ-45) lug. 

Wires fastening should exclude mechanical damage, twisting and abrasion of the wire insulation. 

 

IT IS NOT ALLOWED TO LEAVE EXPOSED PORTIONS OF WIRE PROTRUDING BEYOND THE TERMINAL 

BLOCK. 

 

For a reliable contact, tighten the terminal screws with the force indicated in Table 3.1. 

When reducing the tightening torque, the junction point is heated, the terminal block may be melted and wire can 

burn. If you increase the tightening torque, it is possible to have thread failure of the terminal block screws or the 
compression of the connected wire. 

To improve the performance of the device, it is recommended to install the fuse F1 (fuse element) or its 

equivalent in the EM-481 supply circuit for a current of no more than 2.5 A. 

 
5.1.3.

 Device connection 

5.1.3.1.

 Connect the device as per Fig. 5.1. 

 

5.1.3.2.

 Connect the connection cable to the MODBUS network to the "RS-485" connector and to the MODBUS 

network (or directly to the device with the RS-485 interface). 

 

5.1.3.3.

 If the EM-481 is to connect to the Internet through wired communication, to local network or directly to 

computer, connect the Ethernet connection cable to the Ethernet connector and to the Ethernet network. The details 
of connection depending on the type of wire line are indicated in Appendix B. 

 

5.1.3.4.

 Connect power to the "12 V" power connector. 

 

5.1.3.5.

 If the EM-481 is to connect to the Internet through wireless communication, put SIM card of the telecom 

operator in the SIM slot, and connect the GSM antenna to the ANT connector (SMA F connector). 

 

5.2. Using the device 
5.2.1.

 General 

After  power  is  turned  on,  all  indicators  except 

"LAN"

  and 

"GSM"

  light  up,  and  EM-481  performs  initialization. 

After  that,  for  2  seconds  indicators,  except  for  the  power  indicator,  go  out,  and  the  device  proceeds  to  start  of 
communication  interfaces  with  networks.  In  this  case,  the  display  shows  general  information  about  the  device 
(Fig. 5.2). The start can take up to 15 seconds, depending on settings and the connection quality. 

 
 
 
 

 

 

Figure 5.2

 

– Displaying of general information about the device on the display 

 

After this, the EM-481 goes on to setting connection with the server and querying MODBUS devices. 

 

ATTENTION!  IF  "AL"  LED  PERMANENTLY  ON  OR  PERIODICALLY  BLINKS  AFTER  EM-481  ENABLING 

IT MEANS THE DEVICE FAILURE. 

 

EM-481 provides and supports the connection to Ethernet and GSM

/UMTS

 networks. 

If the 

"LAN"

 indicator lights up, the connection to the network is successful. The blinking 

"LAN"

 LED indicates 

the data is being transmitted through the network. 

If  the 

"GSM"

  indicator  blinks  every  three  seconds,  the  connection  to  the  GSM  network  or  UMTS

 

is  set 

successfully. If the 

"GSM"

 indicator blinks three times per second, then the data is transmitted via GPRS

 

or HSPA. 

The display shows the loads of I/O interfaces and GSM signal level, as shown in Fig. 5.4. 

 
 

 
 
 

 

“E: 5.2k” – the transmission speed via Ethernet is 5.2 kB/s; 
“2G: 7-0.3k” – the GSM signal level is 70 % and the GPRS transmission rate is 0.3 kB/s; 
“S: 15%” – the load of RS-485 is 15 %. 

Figure 5.3

 

– Displaying the status of connections on the display 

 

5.2.2.

 Operation modes 

5.2.2.1.

 Connection to the server 

EM-481 provides and supports connection to the server specified in the settings. If 

“SRV” 

LED

 

is on, it means 

that

 

the  connection  to  server  has  been  done  successfully.  If 

“SRV”

  LED  blinks,  it  means  that  there  is  data 

EM-481 

     © 2018 Novatek-Electro 

FW version 36 

      E: 5.2k              S: 15% 

      2G: 7-0.3k           S: 15% 

Summary of Contents for EM-481

Page 1: ...development and production complies with the requirements of ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device...

Page 2: ...d via RS 485 9 5 2 2 3 Access to MODBUS network using MODBUS TCP 9 5 2 2 4 Access to MODBUS network using SMS 9 5 2 2 5 Data collection and event tracking 10 5 3 Configuration 10 5 3 1 General 10 5 3...

Page 3: ...THE HOUSING IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE DEVICE During operation and maintenance the regulatory document requirements must be met namely Regulations fo...

Page 4: ...ing and transferring data IP protocol is routable protocol for transferring data by Ethernet It is a part of TCP IP and used for Internet IP address is a node address which is unique within a single n...

Page 5: ...showing of warnings about detected faults 4 GSM LED is blinking every 3 sec when there is connection via GSM network or UMTS it is blinking 3 times per second while data exchanging via GPRS or HSPA 5...

Page 6: ...ort circuit output voltage of driver RS 485 maximum mA 250 Resistance of in built terminator Ohm 1000 The recommended number of connected devices in Modbus network when the input current of receivers...

Page 7: ...vice operation Check the device for damage after transportation in case of such damages detection contact the supplier or the manufacturer Carefully study the Operating Manual pay special attention to...

Page 8: ...in the SIM slot and connect the GSM antenna to the ANT connector SMA F connector 5 2 Using the device 5 2 1 General After power is turned on all indicators except LAN and GSM light up and EM 481 perf...

Page 9: ...addresses identifiers If the query could not be redirected for example in the RS 485 slave mode if the connection to the remote MODBUS TCP server was terminated the EM 481 can generate and send the MO...

Page 10: ...ters of address in Ethernet network if Ethernet is used and server address to which EM 481 is connected automatically The adjustable parameters are described in items 5 3 2 The parameters remain saved...

Page 11: ...ess MAC 48 from left to right 6 Table 5 5 Parameters describing the device Parameter Description Address Device type The code that defines the MODBUS product by the manufacturer 23 EM 481 0 Firmware v...

Page 12: ...d access tabs 0 no permission 1 there is permission Bit 6 It is always as 1 Bit 7 Permission for the connected client to configure EM 481 the same as register 121 0 no permission 1 there is permission...

Page 13: ...on to remote server Modbus TCP 0 connection to the remote server is set 1 connecting to the remote server 2 65534 the number of seconds before reconnecting 65535 Connection to the Modbus TCP server is...

Page 14: ...parameters Parameter Range of values Factory setting Description Address Ethernet network Static IP address IP address 192 168 0 111 If the dynamic addressing is switched off or not available IP addre...

Page 15: ...vice provider up to 24 characters 392 415 APN address of host Character string Provided by the GSM service provider up to 34 characters there cannot be spaces in a string 416 449 MODBUS TCP clients Co...

Page 16: ...tart bit 7 data bits 2 stop bits or parity bit and stop bit total is 10 bits The non standard byte formats register 461 values 4 and 5 are not available in this case format 3 2 stop bits is used inste...

Page 17: ...ssword This string should not have any spaces 540 549 The specified password for recording per mission via MODBUS TCP in devices using RS 485 Character string It is used to access devices connected to...

Page 18: ...Gateway Path Unavailable response is not returned to the client 1 255 if there is no connection to the query addressee this exception code is returned to the client 636 Enable RS 485 slave mode 0 1 0...

Page 19: ...aylight saving time 1 10 10 It is used if you selected the automatic transition to daylight saving time on the specified days Week of the month when the clock will be set one hour ahead 1 5 week of th...

Page 20: ...f clock for synchroniza tion s 1 180 2 It is used if you have enabled synchronization of clocks with the server clock The synchronization is performed after receiving the server time if the difference...

Page 21: ...ears once again 5 3 4 EM 481 configuring via MODBUS interface Setting via Modbus interface shall be provided if the device is connected using the Modbus client which is supporting the Modbus TCP proto...

Page 22: ...return and transfer it to the warranty post warranty service please indicate detailed reason for the return in the field of the claims data 8 TRANSPORTATION AND STORAGE The device in the original pack...

Page 23: ...in the GSM network is displayed alternately with the IP address in the local Ethernet network The operation speed with remote Modbus TCP server is improved The speed of GSM operation is increased 30...

Page 24: ...481 Parameter Value Addressing using DHCP Yes IP address 192 168 0 111 Subnet mask 255 255 255 0 Gateway 192 168 0 1 With the factory settings of the EM 481 two ways are possible for communicating wi...

Page 25: ...ter closing the windows answer yes 3 Connection to Internet via Ethernet ATTENTION THE USER IS STRONGLY RECOMMENDED TO CONNECT THE UNIT TO INTERNET UNDER THE SUPERVISION OF THE LAN SYSTEM ADMINISTRATO...

Page 26: ...om the client over the long period the access returns to locked mode ATTENTION DURING ANY CONNECTIONS EXCEPT FOR TRANSMITTING VIA GSM AND COMMUNICATION WITH SERVER VIA SPECIAL PROTOCOL EM 481 THE PASS...

Page 27: ...age in order to delete the device from Overvis system That guarantees that the EM 481 device will be used only by the authorized users Using the instruction on the site of Overvis system connect to EM...

Page 28: ...again the internal memory to re read the program Files can have arbitrary names and extensions and placed in subfolders of the folder TASKS Files placed directly in the folder TASKS allow you to use...

Page 29: ...s The file can contain comment lines that begin with and are ignored when reading the file Correct example Incorrect example This is a comment VARS number of seconds per minute 0 VAL 60 1 VAL 1 This i...

Page 30: ...eters in the task file which are accessed through RS 485 and GSM interfaces By default if no modifier is specified it is 0 PARAMACTUAL ushort Frequency of reading the parameters in seconds It allows o...

Page 31: ...in a single query WRHMULTIPLE uchar uchar Device can write only using function 16 in the storage registers The first argument specifies how many registers can be read in one query the second one deter...

Page 32: ...point 100 F32BLEEP3R 32 bit with reverse order of bytes and floating point 1000 F32WLEEP0R 32 bit with reverse order of words and floating point F32WLEEP1R 32 bit with reverse order of words and floa...

Page 33: ...all variables in the specified range VARSMINIDX var ref var ref The number of the minimum variable in the specified range VARSMAX var ref var ref Maximum of all variables in the specified range VARSMA...

Page 34: ...ref Copy of the condition CONDIS int Set to the specified value The condition is met if the value is not 0 It can be used for adjustment or for unconditional actions for each update cycle NOT cond ref...

Page 35: ...has the following format index action type argument 1 argument 2 Index the sequential number of the line The types of the arguments int 32 bit signed integer alarm reason is the number of reason of t...

Page 36: ...n the text 3 MODBUS ID of the device is OM 310 240 is the register address which is monitored for the fault enabling relay 1 depending on bit 0 of register 240 of device 3 META 8th version of Protocol...

Page 37: ...hieving the temperature respectively the lower or upper limits These registers are read only To change them you should be in configuration mode see it 5 3 4 then write the desired values to addresses...

Page 38: ...VARGEVAR V2 V1 in other cases do not change the hysteresis current value 2 CONDIS 1 VARS the desired hysteresis is selected from V3 V5 according to the conditions of C0 C2 6 VARSSELBYC V3 C0 CONDS is...

Page 39: ...ting select the file of updating The procedure for file selection is given in Table D 2 To cancel the updating cut off the power supply of EM 481 or wait until automatic completion of updating mode Ta...

Page 40: ...Similar to No 2 but the file with an error has less priority The error is automatically corrected with available files of updating 4 The files of updating are not available Escape from the mode of upd...

Reviews: