background image

-

 11

 - 

NOVATEK-ELECTRO                                                                                                                                  EM-481

                                                                                                                                                             

 

Changeable 
settings 

The parameters listed in Table 5.8 that can be changed 
and activated as described in it. 5.3.3 and 5.3.4 

Only in mode of setting, 
reading or writing 

300 

– 799, 

5250 

– 5499 

Active settings  The settings being used by the device at the moment 

In any mode, only 
reading 

2300 

– 2799, 

5500 

– 5749 

Saved settings 

The set is saved regardless the power of the device and 
is used at starting 

Only in mode of setting, 
only reading 

3300 

– 3799, 

5750 

– 5999 

 

Table 5.4

 

– Format of parameters presentation in Modbus registers 

 

Parameter 

Range of values 

Description 

Number of occu-

pied registers 

Number 

– 65535 

Whole  number  (16  bit)  in  standard  range  of  Modbus 
register values 

Number 

-32768  

–  +32767 

Whole number (16 bit) in complementary arithmetic 

Number 

 

4294967295 

In two registers, 

Upper part 

– first 

Whole  number,  which  value  can  exceed  the  limit  for 
Modbus register (65535) 

Number 

-2147483648 

– 

+2147483647 

 in two registers, the upper 

part is the first 

 

Whole number (32 bit) in complementary arithmetic  

 

Character 

string 

In every register 

– number of 

0 to 255 - ASCII character 

code or 0 (the end of string) 

A set of values, each of which is equal to the code of one 
character in the ASCII encoding. If the string is shorter than 
the maximum length, the last character is placed code 0. 

Max. length of 

string for this 

parameter 

IP-address 

(IP-mask) 

In every register 

– one byte 

(0

–255) 

Set of four byte of address IPv4, from left to right 

MAC-address 

In every register 

– one byte 

(0

–255) 

Set of six byte of address MAC-48, from left to right 

 
Table 5.5

 

– Parameters describing the device 

 

Parameter 

Description 

Address 

Device type 

The code that defines the MODBUS product by the manufacturer (23 

– EM-481) 

Firmware version  Firmware version of embedded software 

Check code 

CRC32 of firmware of embedded software 

2

–3 

 
Table 5.6

 

– Parameters of the current mode 

 

Parameter 

Range of 

values 

Initial  

volume 

Description 

Address 

Entering 

password 

String of 

characters 

When  entering  a  valid  password,  the  client  is  given  the 
appropriate permission (see registers 710 - 749). 
When you enter an empty string, the client rights are reset to the 
rights level at the time of connection. 

 100

119 

Control 

command 

0

–40959, 

Writing in 

the 

configura-

tion mode 

0: no activity; 
1: 

“Restart” – EM-481 restart; 

2: 

“Save” – save the changes of settings via

 

MODBUS; 

3:  "Apply"  -  apply  settings  without  restarting  (only  available  for 
MODBUS and user parameters); 
4: "Save and apply" - similarly to commands 2 and 3 sent one after 
another; 
9: 

“Cancel" - to read the saved settings; 

51: 

“Apply for Modbus” – apply settings via Modbus and RS-485; 

59: “Apply for user” – apply settings for the user area of the registers; 

81: “Synchronize clock with NTC server” 

82: “Obtain account balance from GSM operator” 
444: 

“Back  to  Factory  Settings”  -  reset  the  settings  to  the  factory 

settings; 
35381: "Start setting the clock" - it allows access to the registers 
of clock setting; 
35431:  "Cancel  setting  the  clock"  -  it  closes  the  access  to  the 
registers of the clock setting without changing hours; 
40959:  "Clear  the  internal  memory  of  the  tasks"  -  to  erase  the 
program  for  logic  of  actions  (when  the  memory  card  is  inserted,  it 
will automatically read again). 

120 

Table 5.7

 

– Parameters of current state 

 

Parameter 

Description 

Address 

Summary of Contents for EM-481

Page 1: ...development and production complies with the requirements of ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device...

Page 2: ...d via RS 485 9 5 2 2 3 Access to MODBUS network using MODBUS TCP 9 5 2 2 4 Access to MODBUS network using SMS 9 5 2 2 5 Data collection and event tracking 10 5 3 Configuration 10 5 3 1 General 10 5 3...

Page 3: ...THE HOUSING IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE DEVICE During operation and maintenance the regulatory document requirements must be met namely Regulations fo...

Page 4: ...ing and transferring data IP protocol is routable protocol for transferring data by Ethernet It is a part of TCP IP and used for Internet IP address is a node address which is unique within a single n...

Page 5: ...showing of warnings about detected faults 4 GSM LED is blinking every 3 sec when there is connection via GSM network or UMTS it is blinking 3 times per second while data exchanging via GPRS or HSPA 5...

Page 6: ...ort circuit output voltage of driver RS 485 maximum mA 250 Resistance of in built terminator Ohm 1000 The recommended number of connected devices in Modbus network when the input current of receivers...

Page 7: ...vice operation Check the device for damage after transportation in case of such damages detection contact the supplier or the manufacturer Carefully study the Operating Manual pay special attention to...

Page 8: ...in the SIM slot and connect the GSM antenna to the ANT connector SMA F connector 5 2 Using the device 5 2 1 General After power is turned on all indicators except LAN and GSM light up and EM 481 perf...

Page 9: ...addresses identifiers If the query could not be redirected for example in the RS 485 slave mode if the connection to the remote MODBUS TCP server was terminated the EM 481 can generate and send the MO...

Page 10: ...ters of address in Ethernet network if Ethernet is used and server address to which EM 481 is connected automatically The adjustable parameters are described in items 5 3 2 The parameters remain saved...

Page 11: ...ess MAC 48 from left to right 6 Table 5 5 Parameters describing the device Parameter Description Address Device type The code that defines the MODBUS product by the manufacturer 23 EM 481 0 Firmware v...

Page 12: ...d access tabs 0 no permission 1 there is permission Bit 6 It is always as 1 Bit 7 Permission for the connected client to configure EM 481 the same as register 121 0 no permission 1 there is permission...

Page 13: ...on to remote server Modbus TCP 0 connection to the remote server is set 1 connecting to the remote server 2 65534 the number of seconds before reconnecting 65535 Connection to the Modbus TCP server is...

Page 14: ...parameters Parameter Range of values Factory setting Description Address Ethernet network Static IP address IP address 192 168 0 111 If the dynamic addressing is switched off or not available IP addre...

Page 15: ...vice provider up to 24 characters 392 415 APN address of host Character string Provided by the GSM service provider up to 34 characters there cannot be spaces in a string 416 449 MODBUS TCP clients Co...

Page 16: ...tart bit 7 data bits 2 stop bits or parity bit and stop bit total is 10 bits The non standard byte formats register 461 values 4 and 5 are not available in this case format 3 2 stop bits is used inste...

Page 17: ...ssword This string should not have any spaces 540 549 The specified password for recording per mission via MODBUS TCP in devices using RS 485 Character string It is used to access devices connected to...

Page 18: ...Gateway Path Unavailable response is not returned to the client 1 255 if there is no connection to the query addressee this exception code is returned to the client 636 Enable RS 485 slave mode 0 1 0...

Page 19: ...aylight saving time 1 10 10 It is used if you selected the automatic transition to daylight saving time on the specified days Week of the month when the clock will be set one hour ahead 1 5 week of th...

Page 20: ...f clock for synchroniza tion s 1 180 2 It is used if you have enabled synchronization of clocks with the server clock The synchronization is performed after receiving the server time if the difference...

Page 21: ...ears once again 5 3 4 EM 481 configuring via MODBUS interface Setting via Modbus interface shall be provided if the device is connected using the Modbus client which is supporting the Modbus TCP proto...

Page 22: ...return and transfer it to the warranty post warranty service please indicate detailed reason for the return in the field of the claims data 8 TRANSPORTATION AND STORAGE The device in the original pack...

Page 23: ...in the GSM network is displayed alternately with the IP address in the local Ethernet network The operation speed with remote Modbus TCP server is improved The speed of GSM operation is increased 30...

Page 24: ...481 Parameter Value Addressing using DHCP Yes IP address 192 168 0 111 Subnet mask 255 255 255 0 Gateway 192 168 0 1 With the factory settings of the EM 481 two ways are possible for communicating wi...

Page 25: ...ter closing the windows answer yes 3 Connection to Internet via Ethernet ATTENTION THE USER IS STRONGLY RECOMMENDED TO CONNECT THE UNIT TO INTERNET UNDER THE SUPERVISION OF THE LAN SYSTEM ADMINISTRATO...

Page 26: ...om the client over the long period the access returns to locked mode ATTENTION DURING ANY CONNECTIONS EXCEPT FOR TRANSMITTING VIA GSM AND COMMUNICATION WITH SERVER VIA SPECIAL PROTOCOL EM 481 THE PASS...

Page 27: ...age in order to delete the device from Overvis system That guarantees that the EM 481 device will be used only by the authorized users Using the instruction on the site of Overvis system connect to EM...

Page 28: ...again the internal memory to re read the program Files can have arbitrary names and extensions and placed in subfolders of the folder TASKS Files placed directly in the folder TASKS allow you to use...

Page 29: ...s The file can contain comment lines that begin with and are ignored when reading the file Correct example Incorrect example This is a comment VARS number of seconds per minute 0 VAL 60 1 VAL 1 This i...

Page 30: ...eters in the task file which are accessed through RS 485 and GSM interfaces By default if no modifier is specified it is 0 PARAMACTUAL ushort Frequency of reading the parameters in seconds It allows o...

Page 31: ...in a single query WRHMULTIPLE uchar uchar Device can write only using function 16 in the storage registers The first argument specifies how many registers can be read in one query the second one deter...

Page 32: ...point 100 F32BLEEP3R 32 bit with reverse order of bytes and floating point 1000 F32WLEEP0R 32 bit with reverse order of words and floating point F32WLEEP1R 32 bit with reverse order of words and floa...

Page 33: ...all variables in the specified range VARSMINIDX var ref var ref The number of the minimum variable in the specified range VARSMAX var ref var ref Maximum of all variables in the specified range VARSMA...

Page 34: ...ref Copy of the condition CONDIS int Set to the specified value The condition is met if the value is not 0 It can be used for adjustment or for unconditional actions for each update cycle NOT cond ref...

Page 35: ...has the following format index action type argument 1 argument 2 Index the sequential number of the line The types of the arguments int 32 bit signed integer alarm reason is the number of reason of t...

Page 36: ...n the text 3 MODBUS ID of the device is OM 310 240 is the register address which is monitored for the fault enabling relay 1 depending on bit 0 of register 240 of device 3 META 8th version of Protocol...

Page 37: ...hieving the temperature respectively the lower or upper limits These registers are read only To change them you should be in configuration mode see it 5 3 4 then write the desired values to addresses...

Page 38: ...VARGEVAR V2 V1 in other cases do not change the hysteresis current value 2 CONDIS 1 VARS the desired hysteresis is selected from V3 V5 according to the conditions of C0 C2 6 VARSSELBYC V3 C0 CONDS is...

Page 39: ...ting select the file of updating The procedure for file selection is given in Table D 2 To cancel the updating cut off the power supply of EM 481 or wait until automatic completion of updating mode Ta...

Page 40: ...Similar to No 2 but the file with an error has less priority The error is automatically corrected with available files of updating 4 The files of updating are not available Escape from the mode of upd...

Reviews: