background image

-

 21

 - 

NOVATEK-ELECTRO                                                                                                                                  EM-481

                                                                                                                                                             

 

the device, see it. 5.3.1) and select the transition to the specified address (the main page with the tab headings will 
be displayed for switching to other modes). 

 

If the browser is set to use the proxy server, the access to the device via local network shall be granted 
only after adding the IP-address into the exceptions list as indicated in the browser documentation. 

 

2) 

Select “Parameters” for setup of parameters. Password request shall appear before granting access to setup 

mode (factory setting 11111). 

3)  Enter  password  and  press 

ENTER

.  If  the  password  is  correct,  you  shall  be  granted  access  to  the  setup 

mode.  You  will  see  the  settings page.  If  the password  is incorrect,  the  password  request  shall  be  displayed once 
again. 

4)  Settings on the settings page are grouped by types and are divided into tabs. Non-configurable settings and 

measurements are available in the tab "State". Settings on other tabs are listed in Table 5.8. 

5)  Click 

SAVE

 after making changes to the settings. This will check all the changed parameters. If no errors are 

detected,  new  parameters  will  be  stored  in  the 

EM-481

 

memory  (new  settings  will  take  effect  after  the  following 

application of settings or restart of the device). In case of any errors detected upon clicking the SAVE button, none 
of the parameters is saved, while the names of erroneous parameters are highlighted in red. 

6)  To apply the settings without restarting the device, you should click 

"Apply"

 at the bottom of the page. The 

entered settings will be checked. If the values of the parameters have not errors, the parameters will be stored in 
the  memory  of  EM-481  and  will  come  into  force.  Only  parameters  MODBUS  and 

User’s  can  be  applied  without 

restarting. 

7)  To set the clock on the tab "Time", press 

"Set"

 button. 

8)  Click 

"Restore defaults"

 to restore the default value of parameters. 

9)  Click 

"Reset"

 to stop all connections and interrupt all receive/transmit operations, with the following restart 

of the device. In case of any changes to the parameters, either introduced or stored in the memory, these changes 
shall be implemented. 

 

If  the  addressing  parameters  in  Ethernet  network  (MAC-address,  IP-  address)  are  modified  and  saved, 

the  browser  may  not  load  the  page  after  the  restart  of  EM-481 

by  pressing  the  “Reset”  button.  This  can 

happen as the browser continues to reply over the previous address. In this case, the connection should be 
made anew. 

 

10) Clicking the 

“Exit”

 button the will close the setup mode and a password request appears once again. 

 

5.3.4.

 EM-481 configuring via MODBUS-interface 

Setting  via  Modbus-interface  shall  be  provided  if  the  device  is  connected  using  the  Modbus  client,  which  is 

supporting the Modbus TCP protocol. The connection is established using its IP-address (for display of the address 
on the device display see the it. 5.3.1) with the indication of Modbus-identifier (factory setting 

– 111). 

Write the password string into the password input register (see Table 5.6) before setting parameters. Factory set 

password - is 11111, i.e. write 49 - ASCII-code for one to record the factory set password to registers 100 - 104. If 
the password is correct, the mode register (see Table 

5.7) takes the value of “1” - setup mode. 

The  instruction  registers  (see  Table  5.7),  as  well  as  registers  for  the  collection  of  Modbus  customizable 

parameters  (see  Table  5.8)  are  available  for  writing  in  the  setup  mode. When  the  required  value  is  written  to  the 
registers of customizable parameters, write 2 (instruction for 

“Saving”

) in the instruction register. The accuracy of 

values  for  the  stored  parameters  can  be  checked  by  comparing  the  collections  of  customizable  parameters  and 
saved parameters. If collections are the same, new values and settings shall be accepted and saved.

 

To apply the settings without restarting the device you should write into the parameter of the control command the 

value  "4"  -  command 

"Save  and  apply"

.

  Only  parameters  MODBUS  network  and  user

’s  can  be  applied  without  the 

device restarting. The correctness of the saved parameter values can be checked by comparing the sets of configurable 
parameters and current settings. If the sets match, then the new settings are accepted and saved.

 

To  cancel  the  changes  in  the  parameters  before  saving  them,  you  should  write  the  value  of  "9"  command  in  the 

control command parameter - the 

"Cancel"

 command. In this case, the configurable parameters take the values of the 

saved ones. 

To  reset  the  saved  parameters  to  the  factory  settings  in  the  configuration mode,  you  should  write  the  value of 

"444" command in the control command parameter - 

"Reset to factory"

In order for all saved parameter values to take effect, the device must be restarted. Through the MODBUS interface, 

the restart is performed by writing to the parameter of the control command the value "1" - the command 

"Restart"

To  exit  the  setup  mode,  write  0  instead  of  any  character  in  password  input  register.  This  will  clear  all  the 

password input registers and instruction register (turn the values to 0). 

 

6. MAINTENANCE

 

6.1. Safety precautions 

 

THE TERMINALS AND THE DEVICE INTERNAL ELEMENTS CONTAINS POTENTIALLY LETHAL 
VOLTAGE  
DURING MAINTENANCE IT IS NECESSARY TO DISABLE THE DEVICE AND CONNECTED 

    DEVICES FROM THE MAINS. 

Summary of Contents for EM-481

Page 1: ...development and production complies with the requirements of ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device...

Page 2: ...d via RS 485 9 5 2 2 3 Access to MODBUS network using MODBUS TCP 9 5 2 2 4 Access to MODBUS network using SMS 9 5 2 2 5 Data collection and event tracking 10 5 3 Configuration 10 5 3 1 General 10 5 3...

Page 3: ...THE HOUSING IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE DEVICE During operation and maintenance the regulatory document requirements must be met namely Regulations fo...

Page 4: ...ing and transferring data IP protocol is routable protocol for transferring data by Ethernet It is a part of TCP IP and used for Internet IP address is a node address which is unique within a single n...

Page 5: ...showing of warnings about detected faults 4 GSM LED is blinking every 3 sec when there is connection via GSM network or UMTS it is blinking 3 times per second while data exchanging via GPRS or HSPA 5...

Page 6: ...ort circuit output voltage of driver RS 485 maximum mA 250 Resistance of in built terminator Ohm 1000 The recommended number of connected devices in Modbus network when the input current of receivers...

Page 7: ...vice operation Check the device for damage after transportation in case of such damages detection contact the supplier or the manufacturer Carefully study the Operating Manual pay special attention to...

Page 8: ...in the SIM slot and connect the GSM antenna to the ANT connector SMA F connector 5 2 Using the device 5 2 1 General After power is turned on all indicators except LAN and GSM light up and EM 481 perf...

Page 9: ...addresses identifiers If the query could not be redirected for example in the RS 485 slave mode if the connection to the remote MODBUS TCP server was terminated the EM 481 can generate and send the MO...

Page 10: ...ters of address in Ethernet network if Ethernet is used and server address to which EM 481 is connected automatically The adjustable parameters are described in items 5 3 2 The parameters remain saved...

Page 11: ...ess MAC 48 from left to right 6 Table 5 5 Parameters describing the device Parameter Description Address Device type The code that defines the MODBUS product by the manufacturer 23 EM 481 0 Firmware v...

Page 12: ...d access tabs 0 no permission 1 there is permission Bit 6 It is always as 1 Bit 7 Permission for the connected client to configure EM 481 the same as register 121 0 no permission 1 there is permission...

Page 13: ...on to remote server Modbus TCP 0 connection to the remote server is set 1 connecting to the remote server 2 65534 the number of seconds before reconnecting 65535 Connection to the Modbus TCP server is...

Page 14: ...parameters Parameter Range of values Factory setting Description Address Ethernet network Static IP address IP address 192 168 0 111 If the dynamic addressing is switched off or not available IP addre...

Page 15: ...vice provider up to 24 characters 392 415 APN address of host Character string Provided by the GSM service provider up to 34 characters there cannot be spaces in a string 416 449 MODBUS TCP clients Co...

Page 16: ...tart bit 7 data bits 2 stop bits or parity bit and stop bit total is 10 bits The non standard byte formats register 461 values 4 and 5 are not available in this case format 3 2 stop bits is used inste...

Page 17: ...ssword This string should not have any spaces 540 549 The specified password for recording per mission via MODBUS TCP in devices using RS 485 Character string It is used to access devices connected to...

Page 18: ...Gateway Path Unavailable response is not returned to the client 1 255 if there is no connection to the query addressee this exception code is returned to the client 636 Enable RS 485 slave mode 0 1 0...

Page 19: ...aylight saving time 1 10 10 It is used if you selected the automatic transition to daylight saving time on the specified days Week of the month when the clock will be set one hour ahead 1 5 week of th...

Page 20: ...f clock for synchroniza tion s 1 180 2 It is used if you have enabled synchronization of clocks with the server clock The synchronization is performed after receiving the server time if the difference...

Page 21: ...ears once again 5 3 4 EM 481 configuring via MODBUS interface Setting via Modbus interface shall be provided if the device is connected using the Modbus client which is supporting the Modbus TCP proto...

Page 22: ...return and transfer it to the warranty post warranty service please indicate detailed reason for the return in the field of the claims data 8 TRANSPORTATION AND STORAGE The device in the original pack...

Page 23: ...in the GSM network is displayed alternately with the IP address in the local Ethernet network The operation speed with remote Modbus TCP server is improved The speed of GSM operation is increased 30...

Page 24: ...481 Parameter Value Addressing using DHCP Yes IP address 192 168 0 111 Subnet mask 255 255 255 0 Gateway 192 168 0 1 With the factory settings of the EM 481 two ways are possible for communicating wi...

Page 25: ...ter closing the windows answer yes 3 Connection to Internet via Ethernet ATTENTION THE USER IS STRONGLY RECOMMENDED TO CONNECT THE UNIT TO INTERNET UNDER THE SUPERVISION OF THE LAN SYSTEM ADMINISTRATO...

Page 26: ...om the client over the long period the access returns to locked mode ATTENTION DURING ANY CONNECTIONS EXCEPT FOR TRANSMITTING VIA GSM AND COMMUNICATION WITH SERVER VIA SPECIAL PROTOCOL EM 481 THE PASS...

Page 27: ...age in order to delete the device from Overvis system That guarantees that the EM 481 device will be used only by the authorized users Using the instruction on the site of Overvis system connect to EM...

Page 28: ...again the internal memory to re read the program Files can have arbitrary names and extensions and placed in subfolders of the folder TASKS Files placed directly in the folder TASKS allow you to use...

Page 29: ...s The file can contain comment lines that begin with and are ignored when reading the file Correct example Incorrect example This is a comment VARS number of seconds per minute 0 VAL 60 1 VAL 1 This i...

Page 30: ...eters in the task file which are accessed through RS 485 and GSM interfaces By default if no modifier is specified it is 0 PARAMACTUAL ushort Frequency of reading the parameters in seconds It allows o...

Page 31: ...in a single query WRHMULTIPLE uchar uchar Device can write only using function 16 in the storage registers The first argument specifies how many registers can be read in one query the second one deter...

Page 32: ...point 100 F32BLEEP3R 32 bit with reverse order of bytes and floating point 1000 F32WLEEP0R 32 bit with reverse order of words and floating point F32WLEEP1R 32 bit with reverse order of words and floa...

Page 33: ...all variables in the specified range VARSMINIDX var ref var ref The number of the minimum variable in the specified range VARSMAX var ref var ref Maximum of all variables in the specified range VARSMA...

Page 34: ...ref Copy of the condition CONDIS int Set to the specified value The condition is met if the value is not 0 It can be used for adjustment or for unconditional actions for each update cycle NOT cond ref...

Page 35: ...has the following format index action type argument 1 argument 2 Index the sequential number of the line The types of the arguments int 32 bit signed integer alarm reason is the number of reason of t...

Page 36: ...n the text 3 MODBUS ID of the device is OM 310 240 is the register address which is monitored for the fault enabling relay 1 depending on bit 0 of register 240 of device 3 META 8th version of Protocol...

Page 37: ...hieving the temperature respectively the lower or upper limits These registers are read only To change them you should be in configuration mode see it 5 3 4 then write the desired values to addresses...

Page 38: ...VARGEVAR V2 V1 in other cases do not change the hysteresis current value 2 CONDIS 1 VARS the desired hysteresis is selected from V3 V5 according to the conditions of C0 C2 6 VARSSELBYC V3 C0 CONDS is...

Page 39: ...ting select the file of updating The procedure for file selection is given in Table D 2 To cancel the updating cut off the power supply of EM 481 or wait until automatic completion of updating mode Ta...

Page 40: ...Similar to No 2 but the file with an error has less priority The error is automatically corrected with available files of updating 4 The files of updating are not available Escape from the mode of upd...

Reviews: