Troubleshooting
4-15
Part 1603054-02
E
2015 Nordson Corporation
Correction
Message/Condition
Error
Code
907
TCP port already bound
Programming error. Contact Nordson technical support.
908
Listen failed
Programming error. Contact Nordson technical support.
909
File descriptors
exceeded
Programming error. Contact Nordson technical support.
910
No permission to
access serial or TCP
port
Programming error. Contact Nordson technical support.
911
TCP port not available
Programming error. Contact Nordson technical support.
917
Checksum error
Noise in network. Check for loose connections or Ethernet cables
routed parallel to high voltage or VFDs.
918
Invalid frame error
Noise in network. Check for loose connections or Ethernet cables
routed parallel to high voltage or VFDs.
919
Invalid reply error
Noise in network. Check for loose connections or Ethernet cables
routed parallel to high voltage or VFDs.
920
Reply time-out
Noise in network. Check for loose connections or Ethernet cables
routed parallel to high voltage or VFDs.
921
Modbus exception
response
Programming error or remote hardware error. Check node
functions. Refer to manufacturer manual for troubleshooting.
925
Illegal Function
exception response
Programming error or remote hardware error. Check node
functions. Refer to manufacturer manual for troubleshooting.
926
Illegal Data Address
exception response
Programming error or remote hardware error. Check node
functions. Refer to manufacturer manual for troubleshooting.
927
Illegal Data Value
exception response
Programming error or remote hardware error. Check node
functions. Refer to manufacturer manual for troubleshooting.
928
Slave Device Failure
exception response
Programming error or remote hardware error. Check node
functions. Refer to manufacturer manual for troubleshooting.
−
Watchdog Fault
(any remote node
controller fault)
Control program in remote node controller is not running, or
controller has no program installed.
NOTE:
This fault may be a normal response to removing electrical
power from the remote node.
Check the remote node controller mode selection switch. The
switch should be in the run position.
Replace the remote node controller. The replacement must be
pre-programmed or a program must be downloaded and installed in
the field.
Contact Nordson technical support for details.
−
Operation was
successful
Normal operation. No action required.
−
Illegal argument error
Programming error. Contact Nordson technical support.
−
Illegal state error
Programming error. Contact Nordson technical support.
−
Evaluation expired
Programming error. Contact Nordson technical support.
−
I/O error class
Programming error. Contact Nordson technical support.
Fieldbus protocol error
class
Programming error. Contact Nordson technical support.
Obsolete
Summary of Contents for Encore HD iControl System
Page 4: ...Change Record ii Part 1603054 02 E 2015 Nordson Corporation O b s o l e t e ...
Page 8: ...Table of Contents vi Part 1603054 02 E 2015 Nordson Corporation O b s o l e t e ...
Page 22: ...System Overview 2 10 Part 1603054 02 E 2015 Nordson Corporation O b s o l e t e ...
Page 40: ...Installation 3 18 Part 1603054 02 E 2015 Nordson Corporation O b s o l e t e ...
Page 88: ...Parts 6 10 Part 1603054 02 E 2015 Nordson Corporation O b s o l e t e ...
Page 90: ...Wiring Diagrams 7 2 Part 1603054 02 E 2015 Nordson Corporation O b s o l e t e ...
Page 92: ...O b s o l e t e ...