Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
QUICK START COMMISSIONING
4.2.3 - Navigation and menu structure
The drive parameter structure consists of menus (0 to
22) and parameters.
The drive initially powers up so that only the first 10
parameters of Menu 0 can be viewed. The left and right
navigation buttons can only be used to move between
menus if Pr
00.010
has been set to show ‘All Menus’.
Do not change parameter values without
careful consideration. Incorrect values may
cause damage or a safety hazard.
0 1 . 0 1 1
0 0 . 0 0 0
0 1 . 0 1 0
0 1 . 0 0 9
0 2 . 0 0 0
4.2.4 - Saving parameters
When changing a parameter in Menu 0, the new va lue
is saved when pressing the Enter button
to
return to parameter view mode from parameter edit
mode.
If parameters have been changed in the advanced
menus, then the change will not be saved automatically.
A save function must be carried out, see the procedure
below.
Procedure
1. Select ‘SAVE’ in Pr
mm.000
*
2. Either press the red reset button
of the
keypad or toggle the reset digital input.
* Where mm can be any menu number.
4.2.5 - Restoring parameter defaults
Restoring parameter defaults by this method saves the
default values in the drive memory. User security status
Pr
00.010
is not affected by this procedure.
Procedure
1. Ensure the drive is not enabled, i.e. drive is in Inhibit
state.
2. Select ‘Reset 50 Hz Defs’ in Pr
00.000
.
3. Press the red reset button
of the keypad
NOTE
Motor parameters Pr 00.006 to Pr 00.009 are factory-
set. Their values are not affected by a restoring
parameter default procedure.
4.2.6 - Keypad status indications
Upper row
string
Description
Drive
output
stage
Inhibit
The drive is inhibited
and cannot be run.
Disabled
Ready
The drive is ready to
run. The drive enable
is active.
Disabled
Stop
The drive is stopped /
holding zero
frequency.
Enabled
Run
The drive is active and
running.
Enabled
Supply Loss
Supply loss condition
has been detected.
Enabled
Deceleration
The motor is being
decelerated to zero
frequency because
the final drive run has
been deactivated.
Enabled
Dc Injection
The drive is applying
dc injection braking.
Enabled
Trip
The drive has tripped
and no longer
controlling the motor.
The trip code appears
in the lower display.
Disabled
Under Voltage
The drive is in the
under voltage state.
Disabled
Heat
The motor pre-heat
function is active
Enabled
When the drive is in ‘trip’ condition, the upper row of
the display will indicate that the drive has tripped and
the lower row of the display will show the trip code. For
further information regarding trip codes, refer to section
5.2.
During an ‘alarm’ condition, the upper row of the display
alternates between the drive status (Inhibit, Ready or
Run, depending on what is displayed) and the alarm.
For further information regarding alarms, refer to
section 5.3.