24
Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
CONNECTIONS
5
ADIO3
Analog or digital input or
analog output
Default function
Assigned to red, green and
yellow LEDs (flange
options)
Resolution
11 bits
Sample rate
4 ms
Operating as analog voltage input
Type of input
Unipolar single-ended
analog voltage, unipolar
single-ended current or
digital input (positive logic)
or unipolar single-ended
voltage output
Full scale voltage range
0 V to +10 V ±3 %
Maximum offset
± 30 mV
Absolute maximum
voltage range
-18 V to +30 V relative to
0 V
Input resistance
100 kΩ
Resolution
11 bits
Sample rate
4 ms
Operating as analog current input
Current range
0 to 20 mA ± 5 %
Maximum offset
250 μA
Resolution
11 bits
Sample rate
4 ms
Load impedance
165 kΩ
Operating as digital input
Impedance
6.8 kΩ
Input threshold
10 V ±0.8 V (IEC 61131-2,
Type 1)
Operating as voltage output
Full scale voltage range
0 V to +10 V ± 5 %
Minimum load resistance
2 kΩ
Resolution
0.1 %
6
+24 V
11
Function
Supply for external digital
devices
Voltage tolerance
±20 %
Maximum output current
200 mA (total including all
Digital Outputs).
Protection
Current limit and trip
7
DIO1
Digital input / output 1
Default function
ADI1 and ADI2 reference
select
Type
Positive logic digital input
only (for output, with 6-7kΩ
pull down).
Voltage range
0 V to +24 V
Sample rate
4 ms
Operating as an input (default)
Absolute maximum
applied voltage range
-8 V to +30 V relative to 0V
Impedance
6.8 kΩ
Input threshold
10 V ±0.8 V (IEC 61131-2,
Type 1)
Operating as an output
Nominal maximum
output current
50 mA
Maximum output current
200 mA (total, including
+24 Vout)