10
Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
GENERAL INFORMATION
Commander ID300/302
with IE motors
Supply
Commander
ID300 drive
IMfinity
®
Motor
Voltage
Max
input
current
Size
Ref.
Output
Current
4 poles - IE2
4 poles - IE3
2 poles - IE3
Output
power
(V)
(A)
(A)
kW
Hp
230V
1 ph /
3ph
8.1
1
12030
3.0
LSES 80LG
LSES 80LG
LSES 80L
0.75
1.0
9.1
2
22035
3.5
LSES 80LG
LSES 80LG
-
0.9
1.25
12
22052
5.2
LSES 90SL
LSES 90SL
LSES 80LG
1.1
1.5
14.3
22057
5.7
LSES 90L
(1)
LSES 90LU
(1)
LSES 90SL
1.5
2.0
230V
3 ph
10.2
3
32075
7.5
-
LSES 100L
(1)
-
1.8
2.4
12.2
32087
8.7
LSES 100L
(1)
LSES 100LR
(1)
-
2.2
3.0
12.2
32120
12.0
LSES 100LR
(1)
LSES 100LG
(1)
LSES100L
(1)
3.0
4.0
14.8
32155
15.5
LSES 112MU
(1)
LSES 112MU
(1)
LSES 112MG
(1)
4.0
5.0
Supply
Commander
ID300/302 drive
IMfinity
®
Motor
Voltage
Max
input
current
Size
Ref.
Output
Current
4 poles - IE2
4 poles - IE3
2 poles - IE3
Output
power
(V)
(A)
(A)
kW
Hp
400V
3 ph
3.4
1
14021
2.1
LSES 80LG
LSES 80LG
LSES 80L
0.75
1.0
3.5
14025
2.5
LSES 80LG
LSES 80LG
-
0.9
1.25
3.5
14030
3.0
LSES 90SL
LSES 90SL
LSES 80LG
1.1
1.5
3.9
14033
3.3
LSES 90L
LSES 90LU
LSES 90SL
1.5
2.0
7
2
24042
4.2
LSES 90LU
LSES 100L
LSES 90L
1.8
2.4
7.5
24050
5.0
LSES 100L
LSES 100LR
LSES 90LU
2.2
3.0
8
24070
7.0
LSES 100LR
(1)
LSES 100LG
(1)
LSES 100L
(1)
3.0
4.0
9.5
24085
8.5
LSES 112MU
(1)
LSES 112MU
(1)
LSES 112MG
(1)
4.0
5.0
13
3
34119
11.9
LSES 132SU
(1)
LSES 132SM
(1)
LSES 132S
(1)
5.5
7.5
16
34155
15.5
LSES 132M
(1)
LSES 132MU
(1)
LSES 132SM
(1)
7.5
10.0
: Standard motor and drive associations
(1)
For these drive and motor associations, a drive fan is fitted as standard.
NOTE
The Commander ID302 is not available for a 230V supply.
The mains current value is a typical value which depends on the source impedance. The higher the impedance, the
lower the current.