21
Installation and quick start commissioning guide - Commander ID300/302
5511 en - 2017.06 / a
CONNECTIONS
Mains
supply
Max.
input
current
(A)
ID300
ref.
Fuse ratings Cable size
CEI
UL
mm
2
AWG
230V
3 ph
4.5
12017
6
6
1
16
5.3
12024
6
6
8.1
12030
10
10
9.1
22035
16
15
1.5
12
12
22052
16
15
14.3
22057
16
15
10.2
32075
16
15
12.2
32087
16
15
2.5
10
12.2
32120
20
20
14.8
32155
20
20
Mains
supply
Max.
input
current
(A)
ID300
/302
ref.
Fuse ratings Cable size
CEI
UL
mm
2
AWG
400V
3 ph
1.6
14012
6
6
1.5
12
2.2
14015
6
6
2.9
14018
6
6
3.4
14021
6
6
3.5
14025
6
6
3.5
14030
6
6
3.9
14033
10
10
7
24042
10
10
7.5
24050
10
10
8
24070
16
15
2.5
10
9.5
24085
16
15
13
34119
20
20
16
34155
25
25
4
10
NOTE
• The mains current value is a typical value which
depends on the source impedance. The higher the
impedance, the lower the current.
• By default, the switching frequency is set to 3
kHz.
• Commander ID300/302 are suitable for use on a
circuit capable of delivering not more than 5000 rms
symmetrical Amperes, 480V or 230V maximum, when
protected by fuses as specified above.
3.5 -
Power connections
•
It is compulsory to connect the motor to
earth, and earthing must be performed in
accordance with current regulations
(protection of workers).
• When the leakage current exceeds 3.5 mA, a
permanent fixed ground connection must be
provided to the system by using a 10 mm
2
flat
braid. If nee ded, an earthing hole is located on the
motor hou sing and can be used for this purpose,
by ad ding a self-taping screw.
•
Check that the terminal block has been removed
from its fixed holder (unplugged) before making
any connections, so as to avoid putting pressure
on the card.
• Standard Power connections
L1
PE
L2
L3
Optional
EMC filter
Fuses
Mains supply
(3 phases)
Supply
ground
Optional
braking
resistor
(1)
Ground
connection
Drive AC Power
connectors
Already wired
(1)
A thermal overload protection device is included as
standard in the optional braking resistors.
CAUTION
For Commander ID300/302 associated to a brake
motor, please see dedicated power connections on