The POWER LED on the cRIO-905
x
indicates if the power input is in use, as shown in the
following table.
Table 1. POWER LED Indicators
LED Color LED Pattern
Indication
Green
Solid
The cRIO-905
x
is powered on and the connected power supply is
adequate.
—
Off
The cRIO-905
x
is off.
Notice
Do not connect the power connector to a DC mains supply or to any supply
that requires a connecting cable longer than 3 m (10 ft). A DC mains supply is a
local DC electricity supply network in the infrastructure of a site or building.
What to Use
•
Ferrite (included in kit)
•
Screwdriver, 2.54 mm (0.10 in.) flathead
•
Power supply, 9 V to 30 V, 60 W minimum
NI recommends the power supplies listed in the following table for the cRIO-905
x
.
Table 2. NI Power Supplies
Power Supply
Part Number
NI PS-15 Industrial Power Supply
(24 VDC, 5 A, 100 VAC to 120 VAC/200 VAC to 240 VAC input)
781093-01
NI PS-10 Desktop Power Supply
(24 VDC, 5 A, 100 VAC to 120 VAC/200 VAC to 240 VAC input)
782698-01
What to Do
Complete the following steps to connect a power supply to the cRIO-905
x
.
1.
Ensure that your power supply is powered off.
2.
Install the ferrite (National Instruments part number 711849-01, included in the shipping
kit) on the negative and positive leads of the power supply, as shown in the following
figure.
cRIO-905x Getting Started Guide
|