Verify the System IP Configuration
Complete the following steps to verify the system IP configuration of your cRIO-905
x
1.
Put the cRIO-905
x
in safe mode and enable the Console Out feature of the USB Type-C
Device Port with Console Out by holding the RESET button down for 5 seconds.
The STATUS LED starts blinking three times every few seconds.
2.
Use the USB Type-C Device Port with Console Out terminal to read the IP address.
Note
Refer to the
cRIO-905x User Manual
for more information about port
configuration.
3.
Set a new DHCP connection by holding the RESET button down for 5 seconds. The
STATUS LED repeats the same behavior from Step 1.
If the cRIO-905
x
fails to set a new DHCP address, it assigns itself a link-local IP address.
If the DHCP connection is successful and appropriate for your application, skip to Step 6.
4.
In MAX, expand your system under Remote Systems.
5.
Select the
Network Settings
tab to configure the IP and other network settings.
6.
Reboot the cRIO-905
x
by pressing the RESET button.
Configure the Windows Firewall
Use this topic to configure the firewall in Windows to ensure you cRIO-905
x
can
communicate with the network.
•
Use the
Troubleshoot Remote System Discovery
tool to configure the firewall.
1.
In MAX, right click
Remote Systems
and select
Troubleshoot Remote System
Discovery
.
2.
Follow the steps in the tool.
•
Add an exception for MAX to your network firewall or other security software by
completing the following steps:
1.
Select
Start
»
Control Panel
»
Windows Firewall
»
Allow a program through
Windows Firewall
.
Note
For Windows 10, you may need to search for the Control Panel as
it not always available from the Start Menu.
2.
Click
Allow another program
.
3.
Select
Measurement & Automation
.
4.
Click
Add
.
5.
Click
OK
.
•
Ensure that UDP port 44525 is open to communication on the host computer. If you are
using an intelligent switch on the network, ensure that it is not disabling UDP port 44525.
System Reset
The following figure shows the reset behavior of the cRIO-905
x
.
cRIO-905x Getting Started Guide
|