Chapter 2 System Architecture
Page 2- 14
UNIVERGE
NEAX
2000 IPS
Request For Proposal (RFP) Reference Guide
Issue 6
System Power Supply and Cooling Fan
AC/DC Power Supply
The AC/DC Power Card is mounted in the rear side of each MODULAR CHASSIS. The AC/DC Power
card provides power to all circuit cards, which are resided in the MODULAR CHASSIS.
AC power requirements are as follows:
Input Voltage: 85 to 264VAC, 50/60 Hz (Auto sensing 100V/200V selection)
AC/DC Power Card
Description
Qty
Remarks
PZ-PW131
1 per MODULAR CHASSIS
AC/DC Power Supply
5 V, 5.5A, -27 V, 3A
Back-up Power
UPS or battery backup (with external battery) is available for backup power for AC power failure. In
case of battery backup, sealed type battery should be used. The open type battery is not available
because of AC/DC power specifications.
Required Battery Capacity
Battery Backup Time
Required Battery Capacity
10 minutes (Built-in battery)
12VDC, 0.8AH x 2
30 minutes (External battery)
12VDC, 2.2AH x 2
3 hours (External battery)
12VDC, 12AH x 2
Ring Generator Unit (RGU)
The RGU provides ringing supply to analog SLT (PN-4LCAA is no longer required); however, it cannot
ring more than 6 analog SLT’s per MODULAR CHASSIS simultaneously. Therefore, the simultaneous
ringing has to be limited by office data setting.
Ring Generator Unit (RGU) Card
Description
Qty
Remarks
PZ-PW139 MODULAR
CHASSIS
Ring Generator Unit
Ring Voltage: 85/75Vac
Ring Current: 0.05A
Cooling FAN
The cooling FAN is mounted at the right side of each MODULAR CHASSIS. The FAN should be
replaced every 4 years in order to ensure the cooling system.
Cooling FAN
Description
Qty
Remarks
109P0624H
7D09 FAN
1 per MODULAR CHASSIS
Each Modular Chassis is equipped with a
Cooling Fan this part is for replacement only