RSI
Chloride
limit
Water condition
Maximum 65°C / 149°F
and 95°C / 203°F
5.6<RSI<6.2
350 ppm
Slight scale formation
Water treatment not
necessary.
Occasional inspection
recommended.
6.3<RSI<6.8
500 ppm
Neutral water
Water treatment not
necessary.
Occasional inspection
recommended.
6.9<RSI<7.5
350 ppm
Slight corrosion
Water treatment not
necessary.
Occasional inspection
recommended.
7.6<RSI<9.0
200 ppm
Strong corrosion
Regular control necessary.
Use of corrosion inhibitor
recommended
9.1<RSI<11
200 ppm
Very strong corrosion
Regular control necessary.
Use of corrosion inhibitor
recommended
RSI>11
200 ppm
Very strong corrosion
Water cannot be used.
Table 5: Closed loop system
Instruction book
2987 2020 00
75