Symbol
Explanation
pH
Measured pH (at room temperature) of water sample
pH
s
pH at saturation
The pH
s
is calculated by using :
pH
s
= (9.3 + A + B) - (C + D)
Symbol Calculation
A
(
10
log(TDS) - 1) / 10
B
13.12 x
10
log(°C+273) + 34.55
C
10
log(Ca
2+
) - 0.4 (Ca
2+
expressed as ppm CaCO
3
)
D
10
log(M-Alkalinity) (M-Alkalinity expressed as ppm CaCO
3
)
RSI and chloride limitation
RSI
Chlorid
e limit
Water condition
Maximum 65°C /
149°F
Maximum 95°C /
203 °F
RSI<3.9
200
ppm
Very high scale formation
Water cannot be
used.
Not applicable.
4.0<RSI<5.5
200
ppm
High scale formation
Regular control and
descaling operation
necessary.
Not recommended
for plate heat
exchangers
Not applicable.
5.6<RSI<6.2
350
ppm
Slight scale formation
Water treatment not
necessary.
Occasional
inspection
recommended.
Not applicable.
6.3<RSI<6.8
500
ppm
Neutral water
Water treatment not
necessary.
Occasional
inspection
recommended.
Water treatment not
necessary.
Occasional
inspection
recommended.
6.9<RSI<7.5
350
ppm
Slight corrosion
Water treatment not
necessary.
Occasional
inspection
recommended.
Water treatment not
necessary.
Occasional
inspection
recommended.
7.6<RSI<9.0
200
ppm
Strong corrosion
Regular control
necessary.
Avoid interruption of
operation
Regular control
necessary.
Avoid interruption of
operation
Instruction book
2987 2020 00
73
Summary of Contents for VDR 2600
Page 1: ...NANO Refrigerant dryers VDR 2600 VDR 3150 VDR 3700 VDR 4200 VDR 5050 Instruction book...
Page 2: ......
Page 28: ...Figure 17 Electrical diagram Instruction book 26 2987 2020 00...
Page 58: ...Dimension drawing of water cooled dryer imperial units Instruction book 56 2987 2020 00...
Page 59: ...Dimension drawing of air cooled dryer metric units Instruction book 2987 2020 00 57...
Page 62: ...Figure 22 Air cooled dryer Instruction book 60 2987 2020 00...
Page 94: ......
Page 95: ......