Reference
Description
2
Compressed air pipes
All pipes should be installed stress free to the dryer unit.
All pipes should be installed so that there is no
obstruction accessing the unit when the panels are
removed.
The inlet pipe orientation must be straight or with a 90°
upward bend to ensure equal air flow to all internal heat
exchangers.
The compressed air pressure should never exceed the
dryer's design pressure. It is recommended to install a
full flow safety valve at the dryer inlet.
The maximum total pipe length (including
interconnecting piping between dryer and receiver) can
be calculated as follows:
•
Δp = ( L x 450 x Qc ) / ( d x p )
•
L = length of pipe (m)
•
Δp = pressure drop (recommended maximum = 0.1
bar / 1.5 psi )
•
d = inner diameter of pipe (mm)
•
p = absolute pressure at dryer outlet (bar(a))
•
Qc = Free air delivery of the compressor (l/s)
3
Filter (optional)
It is recommended to install a compressed air filter at
the dryer inlet to achieve air purity class: ISO 8573 - 1 :
2010 [2 : - : - ].
The air filter has to be supported and can't be mounted
to the dryer directly without extra supports.
4
Air receiver (optional)
Should be installed in a frost free room on a solid, level
floor.
The preferred position is where the air flow fluctuates
the most:
•
Alternative 1 (6): In front of the dryer when the air
flow from the compressor fluctuates the most.
•
Alternative 2 (7): Behind the dryer when the air
demand fluctuates the most.
Instruction book
62
2987 2020 00
Summary of Contents for VDR 2600
Page 1: ...NANO Refrigerant dryers VDR 2600 VDR 3150 VDR 3700 VDR 4200 VDR 5050 Instruction book...
Page 2: ......
Page 28: ...Figure 17 Electrical diagram Instruction book 26 2987 2020 00...
Page 58: ...Dimension drawing of water cooled dryer imperial units Instruction book 56 2987 2020 00...
Page 59: ...Dimension drawing of air cooled dryer metric units Instruction book 2987 2020 00 57...
Page 62: ...Figure 22 Air cooled dryer Instruction book 60 2987 2020 00...
Page 94: ......
Page 95: ......