closed loop
Reference
Description
(1)
Machine
(2)
Heat exchanger
(3)
Cooling tower
(4)
Make up water
(5)
Blowdown
(6)
Standard Nanospecification
•
the application:
•
standard (max water temperature 65°C / 149°F at the outlet)
Water quality
A full instruction for handling cooling water data is available at Nano.
In case water is not in line with recommended values or if any doubt, please refer to Nano.
Technical specifications
Parameter
Unit
Single Pass
(65°C /
149°F)
Single
Pass
(95°C /
203°F)
Recirculating
(65°C / 149°F)
Closed
System
(65°C /
149°F)
Closed
System
(95°C /
203°F)
1
pH
6.8 - 9.3
6.8 - 9.3
6.8 - 9.3
7.5 - 9.3
7.5 - 9.3
2
Conductivity
µS /
cm
< 1500
< 600
< 4000
< 1500
50 - 600
3
Total
Dissolved
Solids
mg / L
TDS to be measured for calculating RSI.
4
Ca-hardness
ppm
CaCO
3
< 500
< 2
< 500
< 1000
< 50
5
Total Alkalinity
ppm
CaCO
3
No limits indicated. To be measured for calculating RSI.
6
Ryznar
Stability Index
(RSI)
5.6 - 7.5
N.A.
5.6 - 7.5
5.6 - 7.5
5.6 - 7.5
7
Chlorine
ppm
< 0.5
—
< 0.5
—
—
8
Chlorides
ppm
< 500 (*)
< 100
< 500 (*)
< 500 (*)
< 100
9
Nitrates
ppm
No limits indicated. To be measured for calculating RSI.
10
Sulphates
ppm
< 1000
< 200
< 1000
< 400
< 200
11
Chemical
Corrosion
Index
< 5
< 1
< 5
< 1
< 1
Instruction book
2987 2020 00
71
Summary of Contents for VDR 2600
Page 1: ...NANO Refrigerant dryers VDR 2600 VDR 3150 VDR 3700 VDR 4200 VDR 5050 Instruction book...
Page 2: ......
Page 28: ...Figure 17 Electrical diagram Instruction book 26 2987 2020 00...
Page 58: ...Dimension drawing of water cooled dryer imperial units Instruction book 56 2987 2020 00...
Page 59: ...Dimension drawing of air cooled dryer metric units Instruction book 2987 2020 00 57...
Page 62: ...Figure 22 Air cooled dryer Instruction book 60 2987 2020 00...
Page 94: ......
Page 95: ......