4.3
Electric cable size and fuses
Local regulations remain applicable if they are stricter than the values proposed.
For calculations, an undervoltage of 10% is considered and according to
EN60364-5-523, table 52-C11 with installation method E.
Grouping: distance between cables is equal to the cable diameter.
For IEC dryers, the settings of the main fuses below are according to Directive
2014/35/EU (low-voltage directive) EN60204-1. The cable size is valid for cable
PVC 70 ˚C (158 ˚F) at an ambient temperature of 40 ˚C (104 ˚F) / 46˚C (114.8°F).
For cULus dryers, the settings of the main fuses below are according to CSA
standards C22.1 and NFPA70. The cable size is valid for cable PVC 75°C (167°F)
at an ambient temperature of 40°C (104°F) / 46˚C (114.8°F).
Instruction book
2987 2020 00
65