Dryer type
Supply voltage
(V)
Fuse (A)
Fuse type
Supply cable
VDR 4200
400
3x63
gG
1 x (3x 25mm² +
16mm²)
VDR 4200
460
3x60
Type RK1 KTS-R /
type J JKS / type T
JJS (Bussman)
1 x (3x AWG4 +
AWG4)
VDR 5050
380
3x63
gG
1 x (3x 25mm² +
16mm²)
VDR 5050
400
3x63
gG
1 x (3x 25mm² +
16mm²)
VDR 5050
460
3x60
Type RK1 KTS-R /
type J JKS / type T
JJS (Bussman)
1 x (3x AWG4 +
AWG4)
TT/TN.
cULus air-cooled dryers with an ambient temperature of 40 °C / 104 °F
Dryer
Supply voltage
(V)
Fuse (A)
Fuse type
Supply cable
VDR 5050
460
3x60
Type RK1 KTS-R /
type J JKS / type T
JJS (Bussman)
1 x (3x AWG4 +
AWG4)
TT/TN.
cULus air-cooled dryers with an ambient temperature of 46 °C / 114.8 °F
Dryer
Supply voltage
(V)
Fuse (A)
Fuse type
Supply cable
VDR 2600
460
3x50
Type RK1 KTS-R /
type J JKS / type T
JJS (Bussman)
1 x (3x AWG 4 +
AWG 4)
VDR 3150
460
3x50
Type RK1 KTS-R /
type J JKS / type T
JJS (Bussman)
1 x (3x AWG 4 +
AWG 4)
VDR 3700
460
3x60
Type RK1 KTS-R /
type J JKS / type T
JJS (Bussman)
1 x (3x AWG 4 +
AWG 4)
VDR 4200
460
3x60
Type RK1 KTS-R /
type J JKS / type T
JJS (Bussman)
1 x (3x AWG 4 +
AWG 4)
TT/TN.
Instruction book
68
2987 2020 00
Summary of Contents for VDR 2600
Page 1: ...NANO Refrigerant dryers VDR 2600 VDR 3150 VDR 3700 VDR 4200 VDR 5050 Instruction book...
Page 2: ......
Page 28: ...Figure 17 Electrical diagram Instruction book 26 2987 2020 00...
Page 58: ...Dimension drawing of water cooled dryer imperial units Instruction book 56 2987 2020 00...
Page 59: ...Dimension drawing of air cooled dryer metric units Instruction book 2987 2020 00 57...
Page 62: ...Figure 22 Air cooled dryer Instruction book 60 2987 2020 00...
Page 94: ......
Page 95: ......