694 – SD T-Gas
Yellow alarm.
Associated parameter 1.8004.123
Cause
Corrective action
Gas temperature sensor
defective, short circuit or wire
break.
1. Not installed in all engine versions (optional).
2. Check sensor and cabling (B38), replace as necessary.
719 – AL T-Gas L1
Yellow alarm.
Associated parameter 2.8006.034
Cause
Corrective action
Limit value 1 exceeded.
u
Check gas supply.
720 – AL T-Gas L2
Yellow alarm.
Associated parameter 2.8006.035
Cause
Corrective action
Limit value 2 exceeded.
u
Check gas supply.
842 – AL Fuel Throttle Pos. L1
Yellow alarm.
Associated parameter 2.8006.038
Cause
Corrective action
TecJet throttle position has
exceeded limit value 1.
u
Check gas supply.
848 – AL Rel. Humidity L1
Yellow alarm.
Associated parameter 2.8006.039
Cause
Corrective action
Calculated air humidity has
exceeded limit value 1.
u
Check air humidity.
891 – AL Scavenging Active
Yellow alarm.
Associated parameter 2.1090.048
Cause
Corrective action
Engine was shut down by
emergency stop and has failed
to successfully complete the
starting sequence several times.
u
None.
132 | Troubleshooting | MS150121/00E 2015-07