113601 – AL Gas Valve 1 feedback
Red alarm. Initiated by EMU.
Cause
Corrective action
Feedback signal from valve 1
does not correspond with
setpoint signal.
u
Check valve 1 and cabling.
113902 – SS Local Initiated Emerg. Stop
Red alarm. Initiated by EMU.
Cause
Corrective action
Emergency stop detected.
Emergency stop was released
manually (button), or ignition
system reported overspeed.
1. Enable emergency stop.
2. Check governor.
3. Check throttle closing position.
1.4510.186 – Error Status
Red alarm. Initiated by antiknock control.
Cause
Corrective action
Transmission combined alarm.
At least one further transmission
alarm is present.
u
Rectify cause of alarm.
1.4510.187 – Combined Error
Red alarm. Initiated by antiknock control.
Cause
Corrective action
Combined alarm (for details,
refer to the source alarm).
u
Combined alarm (for details, refer to the source alarm).
1.4510.188 – Internal Error
Red alarm. Initiated by antiknock control.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart knock module.
1.4510.189 – Error Camshaft
Red alarm. Initiated by antiknock control.
Cause
Corrective action
No signal from camshaft sensor
for antiknock control.
u
Check cabling. Check sensor B1.3, replace as necessary.
76 | Troubleshooting | MS150121/00E 2015-07