1.4550.032 – A - Stop commanded (Run/Stop)
Yellow alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
ProAct setting is not correct.
u
Check setting.
1.4550.033 – A - Input (Supply) Voltage Fault
Yellow alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
Upper or lower supply voltage
limit reached.
1. Check supply voltage.
2. Check cabling.
1.4550.034 – A - Position Error
Red alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
Position demand and feedback
do not match
u
Check mechanical system. Restart ProAct.
1.4550.035 – A - Temperature Sensor Fault
Red alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart ProAct.
1.4550.036 – A - Temperature derating active
Yellow alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
The internal temperature is
higher than the limit.
1. Check room temperature. Restart ProAct.
2. Restart ProAct.
1.4550.037 – A - Temperature above 120 °C
Red alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
The internal temperature is
higher than the limit.
1. Check room temperature. Restart ProAct.
2. Restart ProAct.
1.4550.038 – A - Loss of Position Demand
Red alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
Position demand is missing or
out of range
1. Check setting.
2. Check cabling.