1.4520.237 – OverSpeed Shutdown
Red alarm. Initiated by IC922.
Cause
Corrective action
Genset has exceeded admissible
speed.
u
Restart ignition.
1.4520.238 – E2PROM Checksum Error
Red alarm. Initiated by IC922.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart ignition.
1.4520.239 – Global Timing out of Range
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Specified global ignition timing
is beyond the valid range.
u
Adjust value.
1.4520.240 – Unknown Timing or Energy Level
Red alarm. Initiated by IC922.
Cause
Corrective action
No global ignition timing and
power level received, CAN bus
connection is faulty.
u
Check cabling and setting.
1.4520.241 – Individual Timing out of Range
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Specified individual ignition
timing is beyond the valid range.
u
Adjust value.
1.4520.242 – Selftest Shutdown
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Self-test is active with the
engine rotating.
u
Restart ignition.
1.4520.243 – Open Primary Rate Exceeded
Red alarm. Initiated by IC922.
Cause
Corrective action
Admissible summation of
discharge faults is reached.
1. Check associated cabling.
2. Check ignition coils.
MS150121/00E 2015-07