606 – AL Double Nodes Lost CAN 1+2
ZKP-Number: 2.0500.691
Red alarm; forced idle
Cause
Corrective action
No communication between
ADEC and PAU.
1. Check wiring and power supply of plant.
2. Acknowledge alarm.
3. Restart engine (→ Page 29).
4. Request towing locomotive if required.
608 – AL Wiring PWM_CM6
ZKP-Number: 1.1041.926
No alarm, fault is entered
Cause
Corrective action
Wire break or short circuit on
channel PWM_CM6.
u
Check wiring to connected device or check connected device
(actuator/sensor), replace if necessary.
609 – AL Wiring PWM_CM7
ZKP-Number: 1.1041.927
Yellow alarm; warning
Cause
Corrective action
Wire break or short circuit on
channel PWM_CM7.
u
Check wiring to connected device or check connected device
(actuator/sensor), replace if necessary.
626 – AL Wiring PWM_CM8
ZKP-Number: 1.1041.928
No alarm, fault is entered
Cause
Corrective action
Wire break or short circuit on
channel PWM_CM8.
u
Check wiring to connected device or check connected device
(actuator/sensor), replace if necessary.
627 – AL Wiring PWM_CM9
ZKP-Number: 1.1041.929
No alarm, fault is entered
Cause
Corrective action
Wire break or short circuit on
channel PWM_CM9.
u
Check wiring to connected device or check connected device
(actuator/sensor), replace if necessary.