Temposonics
®
R-Series
V
EtherNet/IP™
Operation Manual
I 27 I
7.2.1
After completing the EDS wizard, return to the main window
of RSLogix 5000. In the controller organizer sidebar, expand
the I/O Configuration tree and right-click your network. Select
“New Module”.
7.2.2
In the Select Module Type window, choose “R-Series EtherNet/
IP” and click “Create”.
7.2.3
In the New Module window, enter a name in the ‘Name’ field,
select the IP address radio button and enter the static IP
address that is assigned to the sensor. Click “OK” and close the
new module window.
7.2 Add sensor to I/O configuration using EDS file
Fig. 38:
Add a new module to the RSLogix 5000 IO tree
Fig. 39:
Create new moduletree
Fig. 40:
Confirm the new module settings