Temposonics
®
R-Series
V
EtherNet/IP™
Operation Manual
I 16 I
Fig. 20: Replacement of the base unit (e.g. RH5 sensor), part 1
NOTICE
• Secure the base unit screws, e.g. using Loctite 243, before
re-installing.
NOTICE
In the event the R-Series
V
is replacing the R-Series 2004 the plastic
tube must also be remove.
Base unit
Sensor electronics housing
Plastic tube with inner
sensor element
1. Loosen the screws.
3 × socket head screw
M4 (A/F 2.5)
2. Pull out the base unit.
4.5 Replacement of sensor
The base unit of the sensor models RH (RH5-B) is replaceable as
shown in Fig. 20 and Fig. 21. The sensor can be replaced without
interrupting the hydraulic circuit.
3. Insert the new base unit.
Mount the ground lug on a screw.
Tighten the screws.
Fastening torque
1.3 Nm
Fig. 21: Replacement of the base unit (e.g. RH5 sensor), part 2