NOTICE
Step 6.2.7 will make your sensors unique IP address static. It will
disable BOOTP and DHCP, and the IP address will be stored in the
EEPROM of the sensor.
Fig. 29: Request History shows MAC ID and IP address
Fig. 30: Sensor shows the static IP address
6.2.5
Apply power to the sensor. The sensor should take around 10 to
15 seconds to begin to broadcast its MAC ID.
6.2.6
Verify that your IP address and MAC ID appear in the ‘Request
History’ box.
6.2.7
Click to select your sensor in the ‘Relation List’ box and click the
disable BOOTP/DHCP button.
6.2.8
The ‘Status’ message at the bottom of the window will read
“Command Successful” if the disable command was successful.
The sensor is now assigned a static IP address. If needed,
repeat step 6.2.7 until the disable command is successful.
6.2.9
Exit the BOOT/DHCP Server software. If installing the MTS
EtherNet/IP™ EDS file (download at www.mtssensors.com)
continue with chapter 7.1. To utilize the EDS file, the RSLogix
5000 software must be version 20 or later.
If not installing the sensor EDS file, or if using an earlier version
of the RSLogix 5000 software, the sensor parameter data must
be manually loaded. In that case, continue with Steps 2 and 3.