3 Product description
Maschinenfabrik Reinhausen GmbH 2021
21
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
Key
Function
AVR MANUAL
Activating manual mode
In parameterization menu:
Confirm selection
EXTERNAL
CONTROL
Activate voltage regulation via external con-
trol unit
Table 5: Operating elements
Example
To set parameter P2.2, delay time T1, proceed as follows:
1. Press
to activate manual mode.
ð
The LED above the
key lights up.
2. Press
to call up the parameterization menu.
ð
3. Press
to select the menu
P2
.
ð
4. Press
to confirm the selection.
ð
5. Press
to select the parameter P2.2.
ð
6. Press
to confirm the selection.
ð
7. Press
or
to set the desired value (e.g. 15).
ð
8. Press
to accept the selection.
9. Press
to leave the parameterization menu.
ð
The parameter P2.2, delay time T1, is set.
Settings are only saved once the parameterization menu is exited via the
key. If you do not press the
key within 30 s, the parameterization
menu is exited automatically and the changes are not saved.
You will find a detailed description of all control unit parameters and func-
tions in the "Configuring control unit" [