6 Commissioning
Maschinenfabrik Reinhausen GmbH 2021
58
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
6.3.3.1 Cable recommendation
Please note the following recommendation from Maschinenfabrik Rein-
hausen GmbH when wiring the device:
Cable
Terminal
Cable type
Conductor cross-sec-
tion
Max. length
Power supply and voltage
measurement
X1
Unshielded
1.5 mm² with ferrule
2.5 mm² without ferrule
-
Blocking contact
X3
-
Customer messages
X5
-
RS485; SUB-D
X6
Shielded
0.25 mm²
500 m
Optional control cabinet
grounding
-
Unshielded
≥ 16 mm²
-
Table 10: Recommendation for connection cables
The connection cable between the motor-drive unit and the control unit is
supplied as standard.
DANGER
Danger of explosion!
An impermissibly long connection cable between the motor-drive unit and
control unit can lead to malfunctions of the motor-drive unit and the on-load
tap-changer. This allows the on-load tap-changer to remain in an impermis-
sible operating position. This can lead to an explosion in the transformer.
► Only use the connection cable provided.
► The connection cable may not be altered.
6.3.3.2 Electromagnetic compatibility
The device has been developed in accordance with applicable EMC stan-
dards. The following points must be noted in order to meet the EMC stan-
dards.
6.3.3.2.1 Wiring requirement of installation site
Note the following when selecting the installation site:
▪ The system's overvoltage protection must be effective.
▪ The system's ground connection must comply with all technical regula-
tions.
▪ Separate system parts must be joined by a potential equalization.