9 Fault elimination
Maschinenfabrik Reinhausen GmbH 2021
104
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
Characteristics/details
Cause
Remedy
The regulating range of the trans-
former cannot be used.
The parameter "Number of operat-
ing positions (P7)" does not match
the on-load tap-changer.
Check parameter "Number of operating posi-
tions (P7)" [
Regulating range limited.
Check regulating range settings [
Table 21: Problem with automatic voltage regulation (AVR AUTO)
9.3 Other faults
In the event of faults on the on-load tap-changer, motor-drive unit, or control
unit which cannot be easily corrected on site, please inform your authorized
MR representative, the transformer manufacturer or contact Maschinenfabrik
Reinhausen GmbH (MR) directly.
Please have the following data ready:
▪ Serial number (nameplate)
▪ Control unit software version [