8 Control system protocol
Maschinenfabrik Reinhausen GmbH 2021
100
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
8.5 Data points (collective inquiry)
Address
1)
Range
Parameter
Description
Type
Value
R/W
2)
Others
201
0
E1
No connection to EXTERNAL CON-
TROL
0 = ok
1 = error
R
201
1
E2
EXTERNAL CONTROL command
could not be performed
0 = ok
1 = error
R
201
2
3
4
E3.1
E3.2
E3.3
E3.4
Error in connection between control
unit and motor-drive unit
0 = ok
1 = error
R
201
6
E4.1
Automatic adjustment not undertaken
or incorrect
0 = ok
1 = error
R
201
7
E4.2
The desired target position could not
be reached when voltage failed
0 = ok
1 = error
R
201
8
9
10
E5.1
E5.2
E5.3
System not ready
0 = ok
1 = error
R
201
11
12
13
E6.1
E6.2
E6.3
Tap change command cannot be per-
formed
0 = ok
1 = error
R
201
14
15
E7.1
E7.2
Correct positioning not possible
0 = ok
1 = error
R
202
5
n/a
Relay OK
1 = ok
R
202
6
n/a
Relay ERROR
1 = error
R
202
7
E2.1
Highest or lowest operating position
reached
0 = ok
1 = error
R
202
8
E2.2
Previous tap-change operation has not
been completed or fault motor-drive
unit
0 = ok
1 = error
R
202
9
E2.3
Inrush interlock is active or automatic
adjustment required
0 = ok
1 = error
R
202
10
E2.4
Energy in the energy accumulator too
low
0 = ok
1 = error
R
202
11
E2.5
Signal for blocking activated (door in-
terlock or temperature blocking)
0 = ok
1 = error
R
202
12
Motor drive running
1 = motor running
R
202
13
Ready for tap-change operation
1 = ready
R
202
14
Voltage failure
0 = ok,
1 = error
R
202
15
E2.6
No connection to OLTC
0 = ok
1 = error
R
203
0…15
Operating mode
UINT16
1 = AVR AUTO
2 = AVR MANUAL
3 = EXTERNAL
CONTROL
R