7 Operation
Maschinenfabrik Reinhausen GmbH 2021
83
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
To activate or deactivate the "Target position for loss of voltage" function,
proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
3. Press
until the desired parameter is displayed.
ð
4. Press
to confirm the selection.
5. Press
or
to set the desired option.
6. Press
to confirm the selection.
ð
7. Press
until code 3 is displayed.
ð
8. Press
to confirm the selection.
9. Press
to save the setting.
7.4.5 Number of operating positions (P7)
The control unit can be configured for different types of ECOTAP® VPD®
on-load tap-changer. You must set the number of operating positions ac-
cordingly.
When you perform the automatic adjustment (F1.1), the parameter P7 is au-
tomatically set to the correct value.
To set the number of operating positions, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
3. Press
or
to select the desired value.
4. Press
to confirm the selection.