3 Product description
Maschinenfabrik Reinhausen GmbH 2021
18
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
AVR MANUAL manual mode
In AVR MANUAL manual mode, there is no automatic control. The motor-
drive unit can be controlled using the device's operating panel (
= in-
crease voltage,
= reduce voltage). The device settings can be changed.
AVR AUTO auto mode
In auto mode, the device automatically regulates the voltage in accordance
with the set parameters. The voltage is measured in a single phase via the
supply voltage. You have to switch to AVR MANUAL manual mode to config-
ure the control unit.
Control via EXTERNAL CONTROL
In the EXTERNAL CONTROL operating mode, the commands of an external
control unit (e.g. ECOTAP® VPD® CONTROL PRO) are executed. In this
case, manual operation using the RAISE and LOWER keys is not possible.
When operating in this mode, observe the safety instructions and the de-
scription in the external control unit operating instructions.