8 Control system protocol
Maschinenfabrik Reinhausen GmbH 2021
96
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
8 Control system protocol
8.1 Modbus RTU Parameters
The device uses the Modbus RTU (server) control system protocol with the
following parameters:
Parameter
Modbus RTU
Transmission format
RTU
Serial interface
RS485
Baud rate
38,400 baud
Modbus address
1
Number of data bits
8
Parity
Even
Number of stop bits
1
Table 12: Device parameters
8.2 Function codes
Function code
Group name
03
Read holding registers
06
Preset single register
10
Coil holding register
Table 13: Function codes
8.3 Data format
Type
Description
Range
uInt8
unsigned integer 8 bit
0...255
uInt16
unsigned integer 16 bit
0...65 535
sInt16
signed integer 16 bit
- 32 768...+ 32 768
uInt32
unsigned integer 32 bit
0...+ 4.294 967 295 x 10
9
Int64
integer 64 bit
- 9.2 x 10
18
...+ 9.2 x 10
18
float32
32 bit (single precision) in accor-
dance with IEEE 754
IEEE 754
bit16
16 bit-register (each bit has its own
meaning)
-
Table 14: Data format