6 Commissioning
Maschinenfabrik Reinhausen GmbH 2021
66
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
To activate the motor-drive unit and control unit, proceed as follows:
► Switch on medium voltage (transformer is idle).
ð
The control unit starts automatically after a few seconds. The
LED
flashes for 10 s to indicate the inrush interlock. After 10 s, this LED
lights up blue continuously.
ð
The
LED also starts by flashing and then lights up continuously as
soon as the internal energy accumulator is fully charged.
ð
If the
LED is not lit up, then the control unit is ready.
ð
If the red
LED lights up and the
E4
event code is shown in the dis-
play, the automatic adjustment was not carried out correctly.
6.3.7 Setting parameters
Set the most important parameters for commissioning the device in accor-
dance with your requirements:
6. P4.1: Set undervoltage blocking [
7. P4.2: Set overvoltage blocking [
8. P5: Set blocking function [
ð
The most important parameters for voltage regulation have been set.
If you would like to set further parameters, follow section Configuring the
control unit [
6.3.8 Checking automatic voltage regulation
To check the automatic voltage regulation, proceed as follows:
1. Measure voltage on low-voltage side of transformer.
2. Press
to activate the AVR MANUAL operating mode.
3. Press
or
as often as necessary until the measured voltage is be-
yond the range of the set bandwidth (desired voltage ± bandwidth).
4. Press
to activate AVR AUTO operating mode.
ð
After the delay time, the on-load tap-changer moves back into the
range of the set bandwidth. If this does not happen, check the voltage
regulation parameters [