7 Operation
Maschinenfabrik Reinhausen GmbH 2021
75
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
8. Mount the motor-drive unit.
9. Connect the connectors to the terminals X4, X2 and X1 on the control
unit.
7.4 Configuring the control unit
This chapter describes how to configure the control unit.
Settings are only saved once the parameterization menu is exited via the
key. If you do not press the
key within 30 s, the parameterization
menu is exited automatically and the changes are not saved.
7.4.1 Regulation
All of the parameters required for the regulation function are described in this
section.
In AVR AUTO auto mode, voltage regulation works as follows:
▪ If the measured voltage U
actual
is within the set bandwidth
, no control
commands are issued to the motor-drive unit for the tap-change opera-
tion.
▪ Control commands will also not be issued to the motor-drive unit if the
measured voltage returns
to the tolerance bandwidth within the set de-
lay time T1
.
▪ However, if the measured voltage deviates from the set bandwidth for a
longer period
, a tap-change command
occurs after expiration of the
set delay time. The on-load tap-changer carries out a tap-change in a
raise or lower direction to return to the tolerance bandwidth.