CALIBRATION OF TOUCH SCREEN
Calibration of the touch screen has already been completed at the time of product shipment, so basically
no user setting is necessary. Here is explain that the readjustment method when there is an error in the
calibration of the touch screen by some reasons. (If there is an error in the calibration of the touch screen,
the touch area corresponding to the display button will shift, so it will not react even if you touch the display
button.)
If the readjustment becomes frequently necessary, it seems that some trouble has occurred on
the touch screen. In that case we recommend that you submit it for repair.
Step 1: While DigiPack
Ⅲ
powered on, digital signal is continuously input for 3 seconds or longer to TB-
2-8 (this channel displayed as Do not use).
Step 2: DigiPack
Ⅲ
will be automatically restarted and the calibration screen as shown in Figure 1-31 will
be displayed. Touch the "Calibration" button. (At this time, since the calibration information is reset,
"Calibration" button can be pressed)
Step 3: Since Figure 1-32 is displayed, touch all the "+" signs surrounded by the red frame square in the
corner. If you press the wrong place to push, the calibration will fail and the screen will stop re-
sponding. In that case, please turn on the power again, return to step 1 and try again.
Step 4: If the calibration is successful, display will return to Figure 1-31, Restart the controller and finish.
Figure 1-31 Touch screen Calibration
Figure 1-32 Touch screen calibration display